Lamp test
Purpose of the lamp test
Alarms, faults and operating state of the fire detection system are indicated by LEDs in the dis-
play fields, the text display and the alarm buzzer of the control console.
To check the correct function of these parts the
lamp test can be initiated: All visual and audible
devices of the control console are activated for a few seconds.
Frequency
The lamps have to be tested at least once a year.
Lamp test procedure
1.
Press
St
.
Display shows
2.
Select option 4.
2.
2.
1.
To initiate the lamp test.
Display shows
3.
Check:
−
all LEDs on?
−
buzzer audible?
−
missing segments in text display?
If one or more devices are malfunctional, call the SIEMENS service organization.
i
Lamp test on local indication and control panels
page 5.
SELECT: 1. ENabling
(main menu) 2. DISabling
3. INFO polling
4. other functions
TESTING lamps and display:
> remaining time (
→←
↓↑
)
.........................................
.........................................
Summary of Contents for Synova FC330A
Page 4: ...06 2003 II Fire Security Products Siemens Building Technologies Group ...
Page 5: ...e1973c 1 02 2004 1 Fire Security Products Siemens Building Technologies Group Introduction ...
Page 7: ...e1973c 2 02 2004 3 Fire Security Products Siemens Building Technologies Group Fundamentals ...
Page 19: ...e1973c 3 02 2004 15 Fire Security Products Siemens Building Technologies Group Alarm ...
Page 24: ...e1973c 3 02 2004 20 Fire Security Products Siemens Building Technologies Group ...
Page 35: ...e1973c 7 02 2004 31 Fire Security Products Siemens Building Technologies Group Faults ...
Page 37: ...e1973c 8 02 2004 33 Fire Security Products Siemens Building Technologies Group Maintenance ...
Page 46: ...e1973c 12 02 2004 42 Fire Security Products Siemens Building Technologies Group ...
Page 57: ...Back 02 2004 53 Fire Security Products Siemens Building Technologies Group ...