40/148
Siemens Building Technologies
Commissioning instructions OZW775 V2.01
CE1C5663en
HVAC Products
New plant
22.06.2012
3. The following actions are carried out automatically when you create the device list:
−
The central communication unit creates the device list and checks the device
data.
−
The ACS reads the device list from the central communication unit and refreshes
the reference data points for the devices.
Finally, the devices are displayed in "List of assigned devices".
The central communication unit is ready for operation if you do not need to add devices
from other lines (see Section 3.2.2 below).
3.2.2 Add devices
Add devices integrated outside the line or area of the central communication unit on the
Konnex network to the device list.
A plant with "central communication unit type OZW775" exists.
Plant > Edit device
list…
is selected.
1. Right-click field "List of assigned devices" to open the context menu and select
Add devices…
to start adding a device.
2. Dialog box "Insert devices" opens. Click
Add device
Note
Function
Prerequisite
Workflow