Selection
Setting Options
Comment
Limit of Supervi-
sion Command
0 s to 15 s
In steps of 1 s
Supervision time for the transmission of the Supervision
Command.
Exceeding the adjusted value is causing a non-urgent alarm.
If the option Blocking Outputs on Limit of Supervision
Command (in Alarms Control submenu) is active, the
transmission of the supervision command is also stopped.
0 means no limitation.
1)
Only if switching functions in the system configuration or MCM is parameterized.
i
i
NOTE
The MCM mode is only available in the integrated PowerLink.
Configuration of the Command Input
[sccominp-121011-01.tif, 1, en_US]
Figure 3-30
Setting Options for the Command Input
Table 3-38
Setting Options for Input Limitation
Selection
Setting Options
Comment
Limitation of input commands 0 ms to 2000 ms
In steps of 1 ms
Longer pulses result in non-urgent
alarm the command transmission is
interrupted.
3.5.9.2
Installation and Commissioning
3.5 Device Configuration
140
Smart Communication, SWT 3000 Teleprotection, Equipment Manual
C53000-G6040-C605-1, Edition 03.2020