Siemens Building Technologies
Fire Safety
P/N 315-048733-3
7
PROGRAMMING
In order to perform its desired operation, the SSD-C must be programmed using the
Zeus Programming Tool. The SSD properties must be set before normal operation.In
the Zeus Programming Tool, highlight the selected SSD-C module in the
Physical View
and open the
Detail View - Properties
to modify and/or define the following SSD-C
properties:
HNET Address: This address must match the address set in the SSD-C
hardware.
Base Language Custom Message: This message is associated with the
SSD-C module.
Alternate Language Custom Message: This message associated with the
SSD-C module is in an alternate language.
Display Type: Determines the mode configuration of the SSD, either Display-
Only or SSD with Control.
Sounder Enabled: If selected, the sounder activates on event receptions;
otherwise, the sounder is disabled.
Display Alarms: If selected, alarm events are displayed on the SSD; other-
wise, alarm events are filtered.
Display Supervisory Events: If selected, supervisory events are displayed on
the SSD; otherwise, supervisory events are filtered.
Display Security Events: If selected, security events are displayed on the
SSD; otherwise, security events are filtered.
Display Troubles: If selected, trouble events are displayed on the SSD;
otherwise, trouble events are filtered.
WIRING
Disconnect BATTERY and AC prior to working on equipment.
Refer to Figure 5 for a typical wiring connection of
SIEMENS
Model SSD-C to the
FireFinder-XLS System.
FireFInder XLS ENCLOSURE
PSC-12
PMI/CPC
NIC-C
SSD-C
PAIR B (STYLE 7 ONLY)
24VDC (POWER LIMITED)
PAIR A (STYLE 4, STYLE 7)
Figure 5
Typical SSD-C Connection To The FireFinder XLS
NOTES:
1. Compatible wire size:
14 - 18 AWG
2. No EOLR required. S1-1, S1-2
has to be on the ON position
if the SSD-C is at the end of
the Style 4 or Style 7 network.
3. Use twisted pair or twisted
shielded pair
4. Terminate shield at one end
only.
5. Power Limited to NFPA 70
per NEC 760.
6. All wiring is power limited
and supervised.