Use 

●  The SSA911.01TH wireless radiator valve actuator is designed to work on radiator 

valves of different manufacturers in HVAC applications using M30x1.5 thread. It operates 

the valve to control the water flow and controls the room temperature. 

●  The valve actuator works only in combination with Siemens Smart Thermostat 

RDS110.R and optionally with wireless repeater RCR114.1. 

●  One RDS110.R can be paired with up to 6 radiator valve actuators in parallel. Up to 3 

wireless repeaters RCR114.1 can be used to extend the range of the network. 

Smart Thermostat 

RDS (Application) 

RDS110.R 

SSA911.01TH 

RCR114.1 

RDS110.R 

RCR114.1 

SSA911.01TH

Topology with RDS110.R

Topology with RCR114.1

Summary of Contents for SSA911.01TH

Page 1: ...uator communication based on THREAD protocol 2 4 GHz bidirectional Connection and operation with RDS110 R and optionally RCR114 1 Battery powered by commercially available 1 5 V AA batteries Valve thread connection M30x1 5 mm Nominal stroke 2 5 mm Valve positioning force 90 N Automatic adaptation to valve Integrated temperature sensor and PI controller ...

Page 2: ...low and controls the room temperature The valve actuator works only in combination with Siemens Smart Thermostat RDS110 R and optionally with wireless repeater RCR114 1 One RDS110 R can be paired with up to 6 radiator valve actuators in parallel Up to 3 wireless repeaters RCR114 1 can be used to extend the range of the network Smart Thermostat RDS Application RDS110 R SSA911 01TH RCR114 1 RDS110 R...

Page 3: ...onnection to RDS110 R or RCR114 1 is deleted A new pairing process to connect to another Smart Thermostat device starts automatically Adaptation to valve This function starts a new calibration of the SSA911 01TH to the attached valve Factory reset Reset the actuator to factory settings Any existing connection to RDS110 R or RCR114 1 is deleted and the stem is retracted Firmware version Shows the r...

Page 4: ...unscrewed from the radiator valve without the use of a tool Equipment combinations Siemens valves The SSA911 01TH is suited for use with the following types of Siemens radiator valves Type kVS m3 h PN Data sheet VDN1 VEN1 Radiator valves 0 25 1 41 10 CE1N2105 VDN2 VEN2 VUN2 CE1N2106 VD1 CLC 1 9 2 6 CE1N2103 VPD VPE MCV radiator valves 0 02 0 48 CE1N2185 VD1 VE1 Radiator valves 0 25 3 4 CE1N2145 VD...

Page 5: ... Smart Valve Actuator SSA911 01TH Instructions for mounting commissioning and operating SSA911 01TH A5W00046617 Mounting instructions Smart Thermostat RDS110 R Instructions for mounting RDS110 R A5W90008181 Quick guide Smart Thermostat RDS110 R Instructions for commissioning and operating RDS110 R A5W90008183 Smart Thermostat Wireless RDS110 R Data sheet product description A6V11562461 RDS110 R Sm...

Page 6: ... Explosion due to fire or short circuit even with discharged batteries Risk of injury due to flying parts Prevent the batteries from coming into contact with water Do not recharge batteries Do not damage or disassemble batteries Do not beat batteries over 85 C WARNING Leakage of electrolyte Severe burns Handle damaged batteries only wearing suitable protective gloves In case of contact with electr...

Page 7: ... and commissioning of the SSA911 01TH see also Quick guide A5W00046617 1 Mechanical mounting of the SSA911 01TH on the radiator valve Tighten the threaded screw nut firmly by hand do not use tools 2 Remove plastic slip securing the batteries from the SSA911 01TH and wait for the actuator to start up approximately 5 s 3 Press the button on the SSA911 01TH for automatic calibration process 2 s and w...

Page 8: ... for 30 s while a connection test is performed The ID of the connected device will be shown on the RDS110 R display Key lock Shown when pressing the button if key lock mode is activated In key lock mode no manipulation on the actuator is possible Error Shown with error code when an error has occurred Disappears when normal status has been reached again Factory reset Shown during a factory reset pr...

Page 9: ...hat the valve is working correctly and that the valve stem is not stuck and repeat the adaptation Mechanical valve actuator error The movement of the actuator was too short to detect the end positions of the valve Motor movement failure The actuator is not connected to a radiator valve The stroke and or end positions of the valve are not compatible with the SSA911 01TH No controller found pairing ...

Page 10: ...tteries Open the white battery cover 1 Remove the metallic slider 2 Take the batteries out 3 2 Insert new batteries 2 x LR6 Alkaline AA 4 3 Re insert the metallic slider 5 and put the white battery cover back on 6 a The actuator will automatically start a new calibration and after successful calibration will automatically re establish the connection to the Smart Thermostat Unsuccessful pairing or ...

Page 11: ...ical security systems In order to protect plants systems machines and networks against cyber threats it is necessary to implement and continuously maintain a holistic state of the art security concept Siemens portfolio only forms one element of such a concept You are responsible for preventing unauthorized access to your plants systems machines and networks which should only be connected to an ent...

Page 12: ...ring range 0 50 C Internal controller Type PI Degree of protection Protection class Class III according to IEC 60730 1 Protection degree of housing IP 30 1 according to IEC 60529 Pollution degree Class 2 according to IEC 60730 Environmental conditions Operation Temperature 20 54 C Humidity non condensing 65 r h 20 Transportation Temperature 30 45 C Humidity 65 r h 20 Storage Temperature 30 45 C Hu...

Page 13: ...HS compliance material composition packaging environmental benefits disposal Materials and Dimensions Display LCD Housing material Plastic ASA PC color White NCS S 052 G Thread M30x1 5 W x H x D See Dimensions 13 Weight 1 Completely mounted 2 Documents can be downloaded at http www siemens com bt download Dimensions Dimensions in mm kg 0 305 Revision numbers Type Valid from rev no SSA911 01TH S551...

Page 14: ...land Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2020 Technical specifications and availability subject to change without notice Document ID A6V11739247_en _a Edition 2020 10 08 ...