Building Technologies 

Electromotoric Actuators 

CA1N4505en 

HVAC Products 

 

26.10.2006 

SQL36E

 

 

SQL35

, SQL85

 

 

4

1

3

6

Z

0

1

 

 

90 

4

7

1

6

Z

1

6

90 

 

 

Any 

 

Upright to horizontal 

 

Commissioning notes 

When commissioning the complete motorized valve consisting of actuator, mounting kit 
and butterfly valve, always check the wiring and test the functions. This also applies to 
any additional components fitted, e.g. auxiliary switch, potentiometer or auxiliary 
module (variable positioning time). 

VKF41

 or VKF46... butterfly valves can only be commissioned with a SQL35.00 / 

SQL85.00 or SQL36E

 actuator or with an ASK46... manual adjuster fitted. 

To avoid pressure shocks on the butterfly, the VKF46

 must be driven to its fully open 

position (either manually or via positioning signal Y1) prior to activating the pump(s). 

The flow rate is adjusted either by driving the electric actuators as required, or by 
operating the manual adjuster. 

When using a SEZ31.1 auxiliary module set the desired positioning time: 
SQL36E65: 

30...180 s 

SQL36E110: 

60

360 s 

SQL36E160: 

120

720 s 

 

4505Z40

 

«

AUTO

»

 = automatic operation

 

4290Z02

 

«

MAN

»

 = manual operation 

In the case of the SQL36E..., the manual adjuster is always engaged and cannot be 
mechanically disconnected. 
 
The actuators are factory-set to rotate in clockwise direction for opening (as seen from 
the cover). 
 

Position indication 

The adhesive labels supplied must be 
applied during assembly. 

4

5

0

5

Z

4

1

1

2

 

1  Butterfly valve 

 

in 

«

OPEN

»

 position 

2  Butterfly valve 

 

in 

«

CLOSED

»

 position

 

 
 

Orientation 


..











































Warning 

 

Operating mode  

SQL35.00 / SQL85.00 

SQL36E... 

Direction of rotation 

SQL35.00 / SQL85.00

 

Summary of Contents for SQL35.00

Page 1: ...ltage AC 24 V 3 position control signal Nominal angle of rotation 90 Auxiliary switch and potentiometer for extra functions Manual adjuster and position indicator SQL36E built in heating element to avoid condensation SQL36E compatible with EN ISO 5211 flanges SQL36E variable positioning time with SEZ31 1 auxiliary module Use For operation of VKF41 VKF46 and VKF46 TS butterfly valves as control and...

Page 2: ... 554 Z 05 Auxiliary switch and potentiometer 1000 Ω SQL35 00 SQL85 00 1 x ASC9 5 or 1 x ASC9 4 or 1 x ASZ7 4 only one accessory at a time can be mounted SEZ31 1 4505Z10 Auxiliary module for variable positioning time refer to Function mechanical design page 4 SQL36E65 SQL36E110 SQL36E160 ASC36 4505Z 19 Double auxiliary switch ASZ36 0 1000 Ω 4 50 5Z 28 Potentiometer 1000 Ω SQL36E50F04 SQL36E50F05 SQ...

Page 3: ...lves were replaced by VKF46 butterfly valves in 2000 For actuator retrofitting on installed butterfly valves replacement of actuators or ASK35 VKF45 40 125 Use SQL35 00 SQL85 00 actuators and ASK35 VKF45 150 200 Mounting of SQL36E65 actuator recommended Function mechanical design The actuator is driven by a 3 position signal from the controller and generates a rotary motion which is transferred vi...

Page 4: ...adjustable and can therefore be used to achieve longer running times for an angle of rotation of 90 refer to Commissioning Engineering notes The actuators must be electrically connected in accordance with local regulations and with the connection diagrams Regulations and requirements to ensure the safety of people and property must be observed at all times Mounting notes Type Mounting Instructions...

Page 5: ... its fully open position either manually or via positioning signal Y1 prior to activating the pump s The flow rate is adjusted either by driving the electric actuators as required or by operating the manual adjuster When using a SEZ31 1 auxiliary module set the desired positioning time SQL36E65 30 180 s SQL36E110 60 360 s SQL36E160 120 720 s 4505Z40 AUTO automatic operation 4290Z02 MAN manual oper...

Page 6: ...aintenance Before performing any service work on the valve or actuator Switch off the pump and power supply Close the main shut off valves in the pipework Release pressure in the pipes and allow them to cool down completely If necessary disconnect electrical connections from terminals The valve must be re commissioned only with the manual adjuster or the actuator correctly assembled Disposal The a...

Page 7: ...ick N474 Housing protection standard IP 44 to IEC 60529 IP 67 to IEC 60529 Protection class III or II to EN 60730 EN ISO 5211 32mm Flanges and shaft connection to actuator F04 F05 F07 F10 F12 F16 Dimensions weight Dimensions see Dimensions Cable glands 4 x 20 5 mm for M20 2 x M20 Weight 1 4 kg 4 5 kg 7 kg 14 kg 25 kg Materials Housing base yoke die cast aluminium Cover plastic die cast aluminium 1...

Page 8: ...ms Cm1 End switch Cm2 End switch c1 1 auxiliary switch ASC9 5 or c1 c2 1 double auxiliary switch ASC9 4 or c1 1000 Ω 1 built in unit ASZ7 4 1 auxiliary switch and 1 potentiometer N Neutral conductor G System potential Y1 Control phase OPEN Y2 Control phase CLOSED 11 Sequence Y1 at 90 12 Sequence Y2 at 0 S1 End switch CLOSED S2 End switch OPEN S3 Auxiliary switch CLOSED ASC36 S4 Auxiliary switch OP...

Page 9: ... switch CLOSED ASC36 S4 Auxiliary switch OPEN ASC36 S7 Thermal switch integrated H Heating element P1 Potentiometer ASZ36 T1 Auxiliary module SEZ31 1 Y1 Control phase OPEN Y2 Control phase CLOSED N Neutral conductor Connection diagrams 4505A01 L N N Y2 Y1 N2 Y1 Y2 Q1 Q2 Y2 L N L N AC 230 V N Y2 Y1 N1 Y1 Y2 Q1 Q2 Y1 N1 N2 Controller Y1 Y2 Actuator L System potential AC 230 V N System neutral Q1 Q2 ...

Page 10: ...4 V G Y2 Y1 Y2 N1 Q1 Q2 Y1 N1 N2 Controller Y1 Y2 Actuator SP System potential AC 24 V SN System neutral Q1 Q2 Controller contacts Dimensions Dimensions in mm Mounting height of actuator including ASK35 mounting kit 168 mm 100 mm Minimum clearance from wall or ceiling 200 mm For mounting connection operation service etc SQL85 00 SQL35 00 SQL85 00 ...

Page 11: ... M E A 4505M03 G Z Y B L I D H C K J M E A SQL36E50F04 SQL36E50F05 DN 40 65 80 125 A 210 B 73 C 137 D 210 E 65 G Ø 80 H 42 I 126 J 149 K 110 L 259 M 124 X 11 14 Y 42 Z 50 EN 5211 F04 F05 kg 4 5 kg 100 mm Minimum clearance from wall or ceiling 200 mm For mounting connection operation service etc SQL36E50F04 SQL36E50F05 ...

Page 12: ...80 Ø 125 Ø 200 H 42 58 89 I 125 150 175 J 171 247 280 K 119 136 157 L 290 383 437 M 139 139 139 X 17 22 32 Y 70 102 165 Z 50 70 125 EN 5211 F07 F10 2 kg 7 kg 14 kg 25 kg 1 DN 350 400 VKF46 350TS VKF46 400TS 2 EN 5211 F12 F16 flange connections for third party actuators are available on request 100 mm Minimum clearance from wall or ceiling 200 mm For mounting connection operation service etc SQL36E...

Reviews: