Technical Data
14
Siemens Building Technologies
Fire Safety & Security Products
09.2008
3 Technical
Data
3.1 SPC4000
Mains voltage
230 VAC, +10 to -15 %, 50 Hz
Fuse
250 mA T
Power consumption
100 mA @ 230 V AC
Auxiliary power (nominal)
1)
Max. 750 mA @ 12 VDC
Battery Optional
Battery type
Sealed cell valve-regulated
Battery capacity
Max. 7 AH / 12 V
Battery charger
Max. 24h for 80 % of battery capacity
Operating voltage
n.a.
Current consumption
1)
Max. 100 mA @ 12 V DC
Number of on-board zones
8
EOL resistor
Dual 4K7 (default), other resistor combinations configurable
Number of on-board open collector
outputs.
1 internal bell (max. 400 mA resistive),
1 external bell (max. 400 mA resistive),
3 general outputs (each max. 400 mA resistive,
supplied via auxiliary output)
Number of on-board relays
1 strobe, 30 V / 1 A (resistive switching current)
Field bus
2)
X-BUS on RS-485 (307 kb/s)
Interfaces
1 x X-BUS (1 spur),
1 x RS232 (RJ45 ports, for X-10 or external communications),
1 x USB (PC connection for terminal program access),
1 x SPC Fast Programmer
Tamper contact
On-board front cabinet spring tamper
+ 2 auxiliary tamper inputs
Operating temperature
5 - 40 °C
Relative humidity
Max. 90 % (no condensation)
Housing protection
IP30
Colour RAL
9003
Housing protection class
Class II Indoor General
Mounting
Surface, wall mounted
Housing material
Steel, > 1.2 mm
Housing Metal
enclosure
Housing can contain up to
1 additional Expander (size 150 mm x 82 mm)
Standards
Designed to meet
EN50131-1:2006 (Grade 2)
TS50131-3:2003 (Grade 2)
EN50131-6:2008 (Grade 2)
1)
For EN compliance the supplied current needs to be supported by the battery for required stand by time
2)
Max. 400m between devices with cable types IYSTY 2 x 2 x Ø 0,6 mm (min.), UTP cat5 (solid core) or Belden 9829