Tram Detection Applications
Loop Detector Application Notes SLD4
667/HQ/45200/101
17
Note
When interpreting the performance of the detector, there are key points that should be con-
sidered:
10.
Only consider the relay output of the detector when interpreting the performance, for
example via the controller.
11.
The LEDs on the front of the SLD4 detector are an indication, however the output ex-
tension configuration does not influence the LEDs on the front panel.
12.
The vehicle overview on the SLD4 Configuration Tool (Monitoring & Simulation) dis-
plays a filtered version of the raw signal from the detector. This is appropriate for nor-
mal vehicle traffic, but not for trams
4.3.2.
Sticking On
Sticking on,
also be referred to as “flickering”,
occurs when the detector continues to show a
detection after the tram has left the detection area. This can sometimes be caused by vehicles
in adjacent lanes.
To resolve this, increase the threshold, thus decreasing the sensitivity in increments of 0.02
%DL/L at a time until the sticking on issue is resolved.
There is a trade-
off between “sticking on” and “gapping” which may prove difficult to resolve
with setting changes alone. In this very rare case, it may be necessary to move the loop away
from the adjacent lane.