3.8 mA
22.8 mA
20 mA
20.5 mA
4 mA
3.55 mA
①
Normal operation
②
Lower fault current (factory setting)
③
Lower saturation limit (factory setting)
④
Upper saturation limit (factory setting)
⑤
Upper fault current (factory setting)
Upper fault current parameter
Adjusts the magnitude of the upper fault current
⑤
.
Setting range:
Between upper saturation limit
④
und 22.8 mA
Factory setting:
22.8 mA, or as specified in order
3.8 mA
22.8 mA
20 mA
20.5 mA
4 mA
3.55 mA
①
Normal operation
②
Lower fault current (factory setting)
③
Lower saturation limit (factory setting)
④
Upper saturation limit (factory setting)
⑤
Upper fault current (factory setting)
See also
Setting the fault current of the internal transmitter with switch to ≥ 21 mA (Page 175)
9.4.9.2
Lower saturation limit parameter
Sets the lower threshold for the lower saturation limit
③
.
Parameter assignment
9.4 Assigning parameters using remote operation
SITRANS TH100/TH320/TH420/TR320/TR420/TF320/TF420 with 4 to 20 mA/HART
168
Operating Instructions, 05/2020, A5E41864807-AB