Connecting
5.1 Safety information on connecting up
SITRANS TH100
20
Operating Instructions, 06/2010, A5E00331168-02
5.1.2
Safety notes when connecting in hazardous areas
WARNING
Observe the degree of protection
The device must be connected to the supply and signal circuits named in the certificate or
on the nameplate.
When installing the device in hazardous areas:
Use enclosures/connection heads with the degree of protection corresponding to the test
certificate applicable in your country.
WARNING
Electrical connection in hazardous areas
The national directives and laws for hazardous areas valid in your country must be
observed for electrical connection. In Germany these are, for example:
The health and safety at work regulations
The directive for "Installation of electrical systems in hazardous areas", DIN EN 60079-
14 (previously VDE 0165,T1)
The EC type examination certificate
When a auxiliary power supply is needed, check whether the auxiliary power supply
matches that given on the nameplate and with the inspection certificate valid in your
country.
CAUTION
Limited range of use
If the device has been operated outside the ambient conditions specified for potentially
explosive atmospheres, you may no longer operate the device in potentially explosive
atmospheres. Make sure to permanently mask all Ex markings on the nameplate.
NOTICE
Loss of type of protection "Intrinsic safety"
If the transmitter is not operated with an intrinsically-safe power supply, the type of
protection "Intrinsic safety" is no longer guaranteed and the intrinsically-safe approval may
be revoked.
Permanently erase, therefore, the irrelevant types of protection on the nameplate before
commissioning to ensure that erroneous deployment is avoided.
Summary of Contents for SITRANS TH100
Page 28: ...Commissioning SITRANS TH100 28 Operating Instructions 06 2010 A5E00331168 02 ...
Page 32: ...Service and maintenance SITRANS TH100 32 Operating Instructions 06 2010 A5E00331168 02 ...
Page 36: ...Technical data SITRANS TH100 36 Operating Instructions 06 2010 A5E00331168 02 ...
Page 40: ...Spare parts and accessories SITRANS TH100 40 Operating Instructions 06 2010 A5E00331168 02 ...
Page 43: ...Appendix A 2 Control drawing SITRANS TH100 Operating Instructions 06 2010 A5E00331168 02 43 ...
Page 48: ...Glossary SITRANS TH100 48 Operating Instructions 06 2010 A5E00331168 02 ...