Setting the startup characteristics for the SitrFC43 block
Bit = 0: Starting the block in manual mode and in defined position. The totalizers are held (‘Hold’
command). Dosing is switched off (Stop command) if it is configured, and the setpoint is set to
internal.
Bit = 1: The block operates with the last valid commands before CPU-stop, stored at the Oldxxx
inputs, for the totalizers and the dosing unit. These inputs can be read back before a complete
download.
Setting the startup characteristics for Lut400, SipPS2, SitransT, SitransP, SitrP_PA, SitrLRPA, SitrLRHA
and Mr200 blocks
Bit = 0: The most recently stored values are reset on startup
Bit = 1: The most recently used value at the output parameter Out is output on startup.
4.3
Control via auxiliary valve
Feature Bit
Number of the
Feature
bit: 5
Control via a auxiliary valve
You can use this
Feature
bit to specify if control should be performed by a auxiliary valve.
The default setting is 0.
Bit = 0: Control without auxiliary valve / no auxiliary valve present
Bit = 1: Control via auxiliary valve
4.4
Disabling opening and closing
Feature bit
Number of the
Feature
bit: 6
Disabling the Open and Close commands
Only applicable when no auxiliary valve is used (bit 5 = 0)
Bit = 0: Open and Close commands affect control valve
Bit = 1: Disable the Open and Close commands
Configurable response using the Feature I/O
4.4 Disabling opening and closing
SITRANS Library for PCS 7
Function Manual, 05/2019, A5E35351976-11
51