SITRANS FS230
8
A5E38755607-AA, 02/2017
3.2
Installing sensors in Reflect mount
Reflect mount - Sensor installation using mounting frames and spacer bar
1. Use the Wizard setup procedure to program the meter for application parameters such as pipe size, liquid type, and
sensor size. Once entered the transmitter will return a spacing index number appropriate for the application.
2. Using the supplied space bar, set the distance between the sensors according to the spacing index number provided by
transmitter. The spacing index provides the correct distance apart for the sensors based on the pipe size given.
Before continuing refer to the Reflect mount installation diagram example below.
①
Sensor clamping screw
⑥
Spacer bar pin and reference hole
②
Customer pipe
⑦
Mounting strap
③
7ME39600*** Mounting Frame
⑧
Larger pipes may need additional mounting straps
④
Spring Clip (not present on some mounting frame models)
⑨
Orientation for Single path sensor at the 9 o'clock
position
⑤
Spacer bar
⑩
Orientation for Dual path sensor at the 10 and 2
o'clock positions
Figure 3-2
Reflect mount
3.3
Terminal Layout
Figure 3-3
Terminal layout - wall mount housing