BACnet Communications
3.1 BACnet Communications
F US Clamp-on Communications Protocol Manual
30
Hardware Installation Manual, 11/2015, A5E34981613-AC
Device Object
Property Identifier
Description and/or Example Value
R/W
Object_Identifier
BACnetObjectIdentifier
W
Object_Name
{defined by profile selection}
R
Object_Type
DEVICE (8)
R
System_Status
OPERATIONAL (0)
R
Vendor_Name
Siemens Industry, Inc.
R
Vendor_Identifier
313
R
Model_Name
Siemens Option Card
R
Firmware_Revision
2.04.04a
(or later)
R
Application_Software_Version
6.11b (A)
R
Protocol_Version
1
R
Protocol_Revision
4
R
Protocol_Services_Supported
0000010000001011110010000000000011100000
R
Proto-
col_Object_Types_Supported
Device , Analog Input, Binary Input
R
Object_List
{defined by profile selection}
R
Max_APDU_Length_Accepted
1458
R
Segmentation_Supported
3 – no segmentation
R
Local_Time
10:36:13
R
Local_Date
1/21/2013
R
APDU_Timeout
10000
R
Number_Of_ADPU_Retries
3
R
Device_Address_Binding
{}
R
Database_Revision
49
R
Active COV Subscriptions
{}
R
UTC Offset
0
R
Description
-
R
Location
-
R
Analog Input Object
Property Identifier
Description and/or Example Value
Object_Identifier
Unique Identifier (e.g. 8388608)
R
Object_Name
{see Profile List}
(e.g. C1_Ins_Flow_Rate)
R
Object_Type
0 - Analog Input
R
Present_Value
REAL (e.g. 402.3467)
R
Description
Character String (e.g. GAL/MIN)
R
Status_Flags
IN_ALARM,FAULT,OVERRIDDEN,OUT_OF_SERVICE
(e.g. 0000)
R
Event_State
0 - Normal
R
Out_Of_Service
0 - False
R
Reliability
0
R