Technical data
6.1 Input
SITOP PSU400M
34
Manual, 05.2018, C98130-A7601-A1-5-7629
Figure 6-4
Voltage rate of rise
Hot plug in and hot plug out are not permissible!
Maximum voltage rate of rise of the supply voltage: 1
V/μs
Note
Together with the 6EP1566-3AA00 ballast device to limit the voltage rise, hot plug-in and hot
plug-out are permissible.
6EP1566-3AA00
Rated voltage U
in rated
for DC
600 V
Voltage range
200 - 900 V
Input current for DC at rated value of input voltage 600 V:
Rated value
0.85 A