Ambient conditions
SITOP PSU300S
52
Manual, 12.2016, C98130-A7587-A1-7-7629
6EP1433-2BA20 (24 V/5 A)
6EP1434-2BA20 (24 V/10 A)
6EP1436-2BA10 (24 V/20 A)
6EP1437-2BA20 (24 V/40 A)
Damaging gases
Tested according to:
•
EN 60068-2-42 sulfur dioxide
•
EN 60068-2-43 hydrogen sulfide
Atmospheric pressure
Operation:
•
1080 - 795 hPa (-1000 - 2000 m)
•
For operation at altitudes of 2000 m up to 6000 m above sea level:
output must be derated by -7.5% / 1000 m or
the ambient temperature must be reduced by 5 K / 1000 m
see Figure 4-5 Altitude derating (Page 22)
•
Overvoltage category:
II up to 2000 m (EN 60950-1)
I from 2000 m up to 6000 m (EN 60950-1)
Storage:
•
1080 - 660 hPa (-1000 - 3500 m)