Applications
9
9.1
Parallel connection to increase power rating
To increase the power rating, SITOP PSU100L power supplies of the same type can be
directly connected in parallel.
The following must be observed:
●
The cables connected to each power supply at terminals "+" and "-" must have identical
lengths and the same cable cross-sections (or the same impedance) up to a common
external connection point (terminal strip) if possible.
●
The power supplies connected in parallel must be switched on simultaneously with a
common switch in the line feeder cable (e.g. with the main switch available in control
cabinets).
●
The output voltages measured in no-load operation for the power supplies that are not yet
connected in parallel should not deviate more than a maximum of 50 mV. This usually
corresponds to the factory setting. If the output voltage is changed, you should connect
the "-" terminals and then, in no-load operation, measure the voltage difference between
the "+" terminals that have not yet been connected. The voltage difference should not
exceed 50 mV.
Figure 9-1
Parallel connection, correct and incorrect
Summary of Contents for SITOP PSU100L 6EP1332-1LB00
Page 8: ...Safety instructions SITOP PSU100L 8 Manual 08 2016 C98130 A7603 A1 2 7629 ...
Page 20: ...Mounting removal SITOP PSU100L 20 Manual 08 2016 C98130 A7603 A1 2 7629 ...
Page 42: ...Technical data 6 8 Dimension drawing SITOP PSU100L 42 Manual 08 2016 C98130 A7603 A1 2 7629 ...
Page 46: ...Safety approvals EMC 7 4 EMC SITOP PSU100L 46 Manual 08 2016 C98130 A7603 A1 2 7629 ...
Page 56: ...Environment SITOP PSU100L 56 Manual 08 2016 C98130 A7603 A1 2 7629 ...