SITOP power DC-UPS Module 15

English

Protective and Monitoring Functions

Reverse polarity protection:

 The UPS module is electronically protected against polarity reversal of the input voltage and battery.

Overcurrent and short-circuit protection: 

The UPS module is protected by the mains fuse (20 A, type FKS) against overcurrent and short circuits in normal

operation. The fuse on the battery module protects the UPS module against overcurrent in floating operation. An internal current limitation disables floating operation
from a battery current of typically 25-40A. Automatic restart attempts are made every 20 s.

Exhaustive discharge protection:  

Lead-acid batteries may only be discharged down to a certain voltage (exhaustive discharge threshold). Allowing them to

discharge further will reduce their service life and may result in irreparable battery damage. In order to protect the battery against damage, the UPS module is shut
down in store mode and the loads disconnected from the battery as soon as the battery voltage drops below 18.5V DC in floating operation.

Battery test: 

In order to guarantee reliable floating operation, the battery module must be checked to ensure that is it fully functional. For this reason, the connected

battery module is tested every 4 hours in normal operation. The test is carried out only if the battery has not operated in floating mode or been disconnected within
this 4 hour period. The battery test is not performed for applications in which floating operation is activated regularly at shorter intervals. A defective battery is
signaled by a flashing alarm and must then be replaced.

Signaling

"Normal operation", 

i.e. the input voltage at the DC-UPS module is higher than the set cut-in threshold. The loads are being fed by the line-side power supply. If a

battery module is connected, it is fully charged. In normal operation, the green LED (o.k.) is illuminated and relay contact X2.3 – X2.4 (o.k.) closed.

"Floating operation",

 i.e. the input voltage is lower than the set cut-in threshold. The loads are being supplied by the battery module. In floating operation, the

yellow LED (Bat) is illuminated and relay contact X2.2 – X2.3 (Bat) closed (de-energized position when unit is disconnected).

Alarm signal "Battery not ready": 

When the "Battery not ready" signal is active, the red LED (Alarm) is illuminated and relay contact X2.5 – X2.6 (Alarm)

closed (de-energized position when unit is disconnected). Causes for the "battery not ready" state in normal operation are as follows: "Off" operating state, no
battery module connected, reversed polarity or defective battery (battery voltage < 18.5V) or open circuit between battery and UPS module. If the signal flashes in a
1.5s cycle, this indicates that the battery is defective, but still capable of floating operation. The specified buffering times cannot be guaranteed in such cases. The
battery module must be replaced.
The "Alarm" signal in floating operation means that the battery voltage has dropped to <20.4V and automatic disconnection to protect the battery is imminent. When
the battery has been disconnected due to overload, short circuit, exhaustive discharge protection or buffering timeout, the red LED (Alarm) goes out, but relay contact
X2.5 – X2.6 remains closed.
Contact rating:  60V DC / 1A  or 30V AC / 1A

Signal

Text

Battery ready
Battery not ready

BUFRD
ALARM

Normal operation
Not normal operation

DC_OK
DC_LO

Not floating operation
Floating operation

*****

*BAT*

Interface

With module type 6EP1931-2EC11, the three signals are output additionally via a PC-capable RS232

interface. They are each displayed in the form of 5 characters of plain text. The assignment is shown in the table on the
right. When the battery is defective, the signal "Battery ready / not ready" is displayed alternately in a 1.5s cycle. A tool
for reading out and processing the signals is available free of charge on the Internet at http://www.ad.siemens.de/sitop.
This website also contains further information about the interface.
Technical specification: 9600 baud, 8 data bits, 1 stop bit, no parity bit, output every 75ms 

±

 20%, safety separation

according to EN 60950. The connection to the PC is made by means of a continuous 9-way SUB-D extension lead,
(plug/socket), although only 3 pins are needed. (Pin2, Pin3, Pin7)

Environment

Requirements acc. to DIN IEC 721, Part 3-3, Cl. 3K3
Temperature
for storage and shipment:         -40 to +70°C
for operation:                              0 to +60°C
Relative air humidity:  75% yearly average, 95% in 30 days, no condensation
(climate model 3K3 acc. to EN 60721)

Weight

6EP1931-2EC01         0.4kg
6EP1931-2EC11       0.45kg

Standards

Degree of protection: IP20 to EN60529 (VDE 0470 Part1)
Protection class III to EN60950
Safety to VDE 0805 (EN60950): SELV
VDE 0100 Part 410 (IEC 364-4-41)
VDE 0106 Part 1 (IEC 536)
VDE 0113 Part 1 (EN 60204-1)
IEC 1131; CSA C22.2
RI suppression to EN55022, limit-value curve B
Interference immunity to EN 50082-2 incl. Table A2,A3

Installation Instructions

In order to guarantee effective cooling, the unit must be vertically installed such that the input and output terminals are at the bottom. A clearance of at least 50 mm
must be left above and below the unit.

Before commencing with the installation or any repair work, switch off the plant main switch and lock it in the "OFF" position. Please read the operating
instructions for SITOP power.

The fuse on the battery module must be removed before any work is carried out.

Connection and Terminal Assignments

Terminals

Function

Cable cross-section

Cable length

Comments

X1.1

Input voltage DC 24V

1.0 ... 4mm

2

up to 2m

Screw-type terminals for screwdriver with

X1.3

Output voltage DC 24V

17...11 AWG

4.5mm blade width

X1.2/X1.4

Input/output voltage DC 0V

X1.5/X1.6

Battery module DC 24V

up to 2.5m

Recommended tightening torque 0.7-0.9Nm

X2.2,3,4

Signal: Normal operation / Floating operation

0.5... 2.5mm

2

up to 3m

Screw-type terminals for screwdriver with

X2.5,6,7

Signal: Battery not ready / ready

20...13 AWG

up to 3m

3.5mm blade width

X2.8/X2.9

On/Off jumper (no jumper =Off)

up to 3m

Recommended tightening torque 0.5-0.7Nm

X3

RS 232 interface

9-way SUB-D connector, 6EP1931-2EC11 only

!

CAUTION

The external circuitry of all terminals (including signaling contacts) must meet the safety requirements stipulated by VDE 0805 (EN
60950): SELV.

Summary of Contents for SITOP power DC-UPS Module 15

Page 1: ... 1 of 8 SITOP power DC UPS Module 15 SITOP power DC USV Modul 15 6EP1931 2EC01 SITOP power DC UPS Module 15 6EP1931 2EC11 Betriebsanleitung Order No C98130 A7508 A10 01 19 Operating Instructions 6EP1931 2EC01 6EP1931 2EC11 ...

Page 2: ...ren Fall der Aufstellung des Betriebes oder der Instandhaltung berücksichtigen Technische Änderungen jederzeit vorbehalten Note These operating instructions do not purport to cover all details of the product nor to provide for every possible contingency that may arise during installation operation or maintenance Subject to change without notice Einstellung R143 Zuerst Warnhinweise lesen Adjustment...

Page 3: ...uls erfolgt mit einstellbarem Konstantstrom bis zur eingestellten Ladeschlussspannung Ladeschlussspannung UA2 26 3 bis 29 2V DC Ladestrom IA2 0 3 bis 0 7A DC Einstellungen Einstellung der Zuschaltschwelle Sinkt die Eingangsspannung unter den eingestellten Wert der Zuschaltschwelle so schaltet das USV Modul in den Pufferbetrieb um Die Verbraucher werden dann ausschließlich durch das Akkumodul verso...

Page 4: ...nung auf 20 4V gesunken ist und eine Zwangsabschaltung zum Schutz des Akkus unmittelbar bevor steht Nach Abschaltung des Akkus aufgrund Überlast Kurzschluss Tiefentladeschutz oder abgelaufener Pufferzeit erlischt die rote Leuchtdiode Alarm der Relaiskontakt X2 5 X2 6 bleibt geschlossen Belastbarkeit der Relaiskontakte 60V DC 1A oder 30V AC 1A Signal Klartext Pufferbereitschaft vorhanden Pufferbere...

Page 5: ...t current IA1 15A DC Output characteristic of charging regulator The battery module is charged at an adjustable constant current until the set end of charge voltage is reached End of charge voltage vA2 26 3 to 29 2V DC Charging current IA2 0 3 to 0 7A DC Settings Setting the cut in threshold If the input voltage drops below the selected cut in threshold voltage the UPS module switches over to floa...

Page 6: ...isconnection to protect the battery is imminent When the battery has been disconnected due to overload short circuit exhaustive discharge protection or buffering timeout the red LED Alarm goes out but relay contact X2 5 X2 6 remains closed Contact rating 60V DC 1A or 30V AC 1A Signal Text Battery ready Battery not ready BUFRD ALARM Normal operation Not normal operation DC_OK DC_LO Not floating ope...

Page 7: ...5 55 65 75 85 95 105 115 125 135 145 155 165 175 185 195 205 215 225 235 245 255 265 275 285 295 305 315 max 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 x 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 x 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 0 0 0 0 1 1 1 1 x 0 0 1 1 0 0 1 1 0 0 1 1 0 0...

Page 8: ...m Published by Elektronikwerk Wien EWW Electronics Plant Vienna Bereich Group A D Siemensstrasse 88 92 Siemens AG Österreich All rights reserved A 1210 Wien Liefermöglichkeiten und technische Änderungen vorbehalten Delivery conditions and technical content subject to changes ...

Reviews: