background image

SIEMENS AG ÖSTERREICH,  07.2007 

4/ 8 

SITOP modular Redundanzmodul

 

 

 

English

 

!

 

WARNING

 

Hazardous voltages are present in certain parts of this electrical equipment during operation.Incorrect handling of the 
equipment can result in death, severe personal injury or substantial property damage. Only qualified personnel are allowed to 
work on or around this equipment.

 

The successful and safe operation of this equipment is dependent on proper transport, 

storage and installation. 
Before installation or maintenance work is carried out, the mains switch must be switched off and locked to prevent it from 
being switched on again. If these rules are not adhered to, contact with live parts or improper use can result in death or 
severe personal injury.

 

 

    

 

CAUTION

 

The device may only be opened by qualified personnel. 

Electrostatically sensitive devices (ESD)

 

Description  

The additional module for redundant mode of 2 supplies is a built-in device belonging to the SITOP series. 

The device must be installed taking into account all relevant DIN/VDE specifications and other national standards. 

It is used in combination with two stabilized 24V load power supply units to implement a redundant 24V supply. If one of the power supplies 
fails, the other will supply the load. 
For this purpose the redundance module is connected in parallel mode with the SITOP load power supply units. The "In 24V-1” and “In 24V-
2" inputs of the redundance module must be connected to the "+" outputs of the power supply units, and the "Gnd" input of the redundance 
module to the  "-" outputs of the power supply units. The “Out 24V” output must be connected with the load (see wiring information on page 
2). The output cable of the redundancy module has to be wired up in a wire cross-section that can

 

carry the maximum total current of both 

infeeding power supplies.

 

 

The failure of one of the 24V power supplies will be signalized via an LED and a relay contact. The response threshold of this signaling 
system can be set using a potentiometer on the redundance module in the range from 20V to 25V. 

 

!

 

Caution

: The redundance module is suitable for the redundant setup of two SITOP power supplies up to a rated output current of 20A 

each! For the redundant setup of 2 power supplies with 30A or 40A rated output current, two redundance modules will be necessary.  In this 
case one redundance module is assigned to one power supply respectively and the terminals “In 24V-1” and “In 24-2” need to be 
interconnected on each module.  

 

 

Technical data  

Input variables 

Rated input voltage U

e

24V DC 

Operating voltage range: 
22...28.8V DC 

Output variables

 

Output DC voltage U

a

U

e

 – approx. 0,5V 

Output DC current I

a

:  

0…40 A 

Max.Output sum current I

a

40A 

 

 

 

Signaling 

Green LED: 
both Input voltages > switching threshold  

Red LED: 
at least one input voltage < switching threshold 

Floating relay contact:  
message o.k. if both Input voltages > switching threshold, 
contact rating: 6 A / 240 V~ 

Setting range of threshold: 
20V 

±

  0.5V... 25V 

±

  0.5V 

Ambient 

Temperature 
Storage and transport:   -25 to +85°C  [-13 to 185°F] 
Operation:                         0 to +60°C  [32 to 140°F] 

 

 

Humidity rating corresponds to climatic category 
3K3 acc. to EN 60721 Part 3, no condensation 

Natural air cooling 

Specifications 

Degree of protection: IP20 acc. to IEC 529 

Safety class 1 acc. to IEC 536 

Safety acc. to VDE 0160 and VDE 0805  
(EN 60950): SELV 

Emitted interference acc. to EN 50081-1 
Radio interference suppression acc. to EN 55022, 
limit curve B 

Noise immunity acc. to EN 61000-6-2 

cULus (UL 508, CSA 22.2 No.14-M95),                     
File E197259    

ATEX  (Ex) II 3 G, Ex                                                 
nAC IIC T4 U  

Weight 

1,0kg   [2,2 lb.]

 

Installation

 

Mounting on a DIN EN 50022-35x15/7.5 standard rail. To ensure adequate cooling, the device must be installed vertically, with the terminals 
at the bottom. Be sure to leave a minimum clearance of 50mm above and below the device. 

 

Connections and terminal assignment 

 

Terminals Function 

Terminal 

range 

Remarks 

In 24V-1 

Max. output summation current : 

In 24V-2 

Input 24V supply voltage from power supply 2 

Out 24V 

Output 24V supply voltage to the load 

Gnd 

0V connection to the internal supply 

0.33 to 10mm

[AWG 22 to 8] 

Screw-type terminals. Use a screw driver with a 
blade width of 5mm. Recommended tightening 
torque 1,2Nm. 

ok 

Floating relay contact (changeover contact) 

0,5 to 2,5mm

[AWG 24 to 12] 

Screw-type terminals. Use a screw driver with a 
blade width of 3mm. Recommended tightening 
torque 0,5…0,6Nm 

Summary of Contents for SITOP modular 6EP1961-3BA20

Page 1: ...07 2007 1 8 SITOP modular Redundanzmodul SITOP modular 6EP1961 3BA20 Redundanzmodul Redundance module Betriebsanleitung Best Nr C98130 A7556 A1 04 6419 Operating instructions Instructions Istruzioni di servizio Instrucciones ...

Page 2: ...our des raisons de clarté cette notice ne contient pas toutes les informations de détail relatives à tous les types du produit et ne peut pas non plus tenir compte de tous les cas d installation d exploitation et de maintenance imaginables Pour de plus amples informations veuillez vous adresser à votre agence Siemens ou consultez notre site http www siemens de sitop Sous réserve de modifications t...

Page 3: ...ntiometer am Diodenmodul im Bereich von 20V bis 25V eingestellt werden Achtung Das Diodenmodul ist geeignet für den redundanten Aufbau zweier SITOP Stromversorgungen bis zu einem Nennausgangsstrom von je 20A Bei redundantem Aufbau zweier Stromversorgungen mit 30A bzw 40A Nennausgangsstrom sind zwei Diodenmodule notwendig wobei jeweils ein Modul einer Stromversorgung zugeordnet wird Dabei sind die ...

Page 4: ...ance module is suitable for the redundant setup of two SITOP power supplies up to a rated output current of 20A each For the redundant setup of 2 power supplies with 30A or 40A rated output current two redundance modules will be necessary In this case one redundance module is assigned to one power supply respectively and the terminals In 24V 1 and In 24 2 need to be interconnected on each module T...

Page 5: ...mètre sur le module de redondance Attention Le module de redondance convient pour la mise en redondance de deux alimentations SITOP de courant de sortie nominal maximal 20A chaque Le couplage redondant de deux alimentations à courant de sortie 30A ou 40A exige deux modules à diodes chacun des deux étant associé à une alimentation Il faudra alors relier les entrées In 24V 1 et In 24V 2 sur chacun d...

Page 6: ...tenzione Il modulo di ridondanza è idoneo per una struttura ridondante di due alimentatori SITOP con una corrente nominale di uscita fino a 20 A Nelle strutture ridondanti di due alimentatori con 30 A opp 40 A di corrente di uscita sono necessari due modulo di ridondanza di cui ognuno viene abbinato ad un modulo alimentatore I collegamenti In 24V 1 e In 24V 2 di ogni modulo vanno collegati tra di ...

Page 7: ...ión el módulo de redundancia es idóneo para instalar una alimentación redundante utilizando dos fuentes SITOP con una intensidad nominal de salida de 20ª cada una Para una instalación redundante con dos fuentes con 30A y 40A respec de intensidad de salida se requieren dos módulo de redundancia cada uno de los módulos deberá asignarse a una fuente de alimentación Para ello es necesario conectar ent...

Page 8: ...stell Nr C98130 A7556 A1 04 6419 Printed in Austria BA 07 2007 Herausgegeben von SIMEA Bereich A D Siemensstraße 88 92 Siemens AG Österreich All rights reserved A 1210 Wien Liefermöglichkeiten und technische Änderungen vorbehalten ...

Reviews: