Getting Started 

 

4.3 CFC 

3.

 

A dialog similar ri the input address opens. Enter output address, in this case: QW0. 

 

4.

 

Confirm value by pressing enter. Now the blocks output address is connected to the 

devices output address. 

Block set up is now complete. 

Generate module drivers 

1.

 

Go to Chart > Compile > Chart as Program or hit Ctrl+B or click

 in the toolbar. 

Compile dialog opens. 

2.

 

Ensure that the option Generate module drivers is checked in. Confirm dialog with the 

OK-Button. 

 

3.

 

After compilation has finished, Logs dialog will be displayed. Confirm this dialog by the 

Close button. 

4.

 

Now hit F5 in the chart view. The view will be updated and all textual interconnections are 

replaced by the according block interconnection. 

 

PCS 7 Library Soft Starter 3RW44 "V6.2" / "V7.1" / "V8 Migration V8.0+SP2 

22

 

Getting Started, 05/2015, A5E02897713020A/RS-AB/004 

Summary of Contents for Sirius 3RW44 V.6.2

Page 1: ...d Industrial Controls Function Block Library Soft Starter SIRIUS 3RW44 for SIMATIC PCS 7 PCS 7 Soft Starter 3RW44 V6 2 V7 1 3RW44 Soft Starter PCS 7 Library V8 Migration V8 0 SP2 Edition 05 2015 Answers for industry ...

Page 2: ......

Page 3: ...______________ ___________________ ___________________ ___________________ Industrial Controls PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 Getting Started 05 2015 A5E02897713020A RS AB 004 Preface 1 Security information 2 Introduction 3 Getting Started 4 References 5 List of Abbreviations 6 ...

Page 4: ...sonnel are those who based on their training and experience are capable of identifying risks and avoiding potential hazards when working with these products systems Proper use of Siemens products Note the following WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation If products and components from other manufacturers a...

Page 5: ...duction 13 4 Getting Started 15 4 1 Installation 15 4 2 HW Config 16 4 3 CFC 17 4 4 Operator Station 24 5 References 31 6 List of Abbreviations 33 6 1 Abbreviations 33 PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 Getting Started 05 2015 A5E02897713020A RS AB 004 5 ...

Page 6: ...Table of contents PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 6 Getting Started 05 2015 A5E02897713020A RS AB 004 ...

Page 7: ... 7 V7 0 SIMATIC PCS 7 Process Control System V7 0 Getting Started First Steps Documentation For PCS 7 V7 1 Process Control System PCS 7 Getting Started Part 1 V7 1 Process Control System PCS 7 Getting Started Part 2 V7 1 For PCS 7 V8 0 Process Control System PCS 7 Getting Started Part 1 V8 0 Process Control System PCS 7 Getting Started Part 2 V8 0 Conventions This documentation contains designatio...

Page 8: ...ol System PCS 7 V6 1 Released Modules SIMATIC Process Control System PCS 7 Released Modules V7 1 SIMATIC Process Control System PCS 7 Released modules V8 0 You create the PCS 7 project with the SIMATIC Manager To create a project in PCS 7 follow the instructions in the documentation Process Control System SIMATIC PCS 7 V6 0 Getting Started First Steps Documentation or Process Control System SIMATI...

Page 9: ...r Description 6ES7416 3XL04 0AB0 SIMATIC S7 400 CPU 416 3 central processing unit e g with PROFIBUS DP interface 6ES7407 0KA01 0AA0 SIMATIC S7 400 Power Supply PS 407 10 A UC 120 230 V DC 5 V 10 A Note Creating a PCS 7 project Create the PCS 7 project with the automation station AS hardware listed in the table above this note Table 1 3 Hardware Automation station 2 Configuration following a Y link...

Page 10: ...Preface PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 10 Getting Started 05 2015 A5E02897713020A RS AB 004 ...

Page 11: ... of Siemens products and solutions it is necessary to take suitable preventive action e g cell protection concept and integrate each component into a holistic state of the art industrial security concept Third party products that may be in use should also be considered For more information about industrial security visit http www siemens com industrialsecurity To stay informed about product update...

Page 12: ...Security information PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 12 Getting Started 05 2015 A5E02897713020A RS AB 004 ...

Page 13: ...configuration can be done by the user as well User manual and online help will give detailed information about the blocks and their input and output pins Any manual changes done in the interconnections between the blocks can be reverted by running the driver generator again This will reset all interconnections to initial state This document will guide you through the necessary steps for using the ...

Page 14: ...Introduction 3 1 Introduction PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 14 Getting Started 05 2015 A5E02897713020A RS AB 004 ...

Page 15: ...nts for Automation System OS Components for Operator Station For example this library has 3RW44 Soft Starter PCS 7 Library V8 AS Migration V8 0 SP2 3RW44 Soft Starter PCS 7 Library V8 OS Migration V8 0 SP2 Installation program will ask you to decide which product you want to install Please take a look at the decision matrix AS OS Single Station X X AS OS Distributed System Engineering Station X Op...

Page 16: ...Config to retrieve the input and output addresses of the Soft Starter device Note down the addresses or enter them in symbol table for later usage PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 16 Getting Started 05 2015 A5E02897713020A RS AB 004 ...

Page 17: ...data library proceed with the following steps CFC Template 1 Open CFC Editor by double clicking on the desired CFC Object 2 Select the Libraries tab located underneath the Catalog view If the Soft Starter template is placed in the Master data library you will find it in the project library folder Notation Project Name _Lib e g GS_SoSt_Lib Otherwise you will find the Soft Starter Template in the So...

Page 18: ...Expand the Charts node The SoftStarter template is present 5 Drag the SoftStarter object by pressing left mouse button and drop the object in the Chart view SoftStarter template is now instantiated PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 18 Getting Started 05 2015 A5E02897713020A RS AB 004 ...

Page 19: ... Right click on the instantiated SoftStarter template in the chart view and select Open The template opens in a new chart view PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 Getting Started 05 2015 A5E02897713020A RS AB 004 19 ...

Page 20: ... input address Since this is a short example we will just hand over the device input address as it is displayed in HW Config We recommend using the symbol table for large projects Please refer to SIMATIC Process Control System PCS 7 Engineering System 2 Right click on Input WORD address of Soft Starter Module IW x and select Interconnection to Address A symbol table like dialog opens PCS 7 Library...

Page 21: ...dress Output 1 Please note the following label in the CFC Template This is a reminder that you need to wire the output address of the Soft Starter device manually 2 Right click on output pin OUT_01 of block SS_DIR and select Interconnection to Address PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 Getting Started 05 2015 A5E02897713020A RS AB 004 21 ...

Page 22: ...it Ctrl B or click in the toolbar Compile dialog opens 2 Ensure that the option Generate module drivers is checked in Confirm dialog with the OK Button 3 After compilation has finished Logs dialog will be displayed Confirm this dialog by the Close button 4 Now hit F5 in the chart view The view will be updated and all textual interconnections are replaced by the according block interconnection PCS ...

Page 23: ...e Deactivate Generate module drivers if you want to keep your changes Download The CFC Template is now ready for download Go to CPU Download or hit CTRL L or use in the toolbar Template set up is now complete and ready to use PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 Getting Started 05 2015 A5E02897713020A RS AB 004 23 ...

Page 24: ...tor Station Block Icons After activating WinCC you will find three block icons for the Soft Starter device The block icons in detail are SSDIR Control Soft Starter SSMEAS Measurement values SSSTAT Statistic values The block icons give a general feedback of the current device status to the user You can find the detailed information about the device in the faceplate PCS 7 Library Soft Starter 3RW44 ...

Page 25: ...ting Started 4 4 Operator Station Faceplates Faceplates of the block icons SSDIR SSMEAS PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 Getting Started 05 2015 A5E02897713020A RS AB 004 25 ...

Page 26: ...nce Process image Parameter Parameter set1 Parameter set2 Parameter set3 Station diag Control diag Device diag Parameter diag Logbook Alarm Batch Trend Standard Standard 2 Protection diag Alarm Trend Batch Standard Max Pointer PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 26 Getting Started 05 2015 A5E02897713020A RS AB 004 ...

Page 27: ... pinned or unpinned to the screen according to the demands of the user Further information on how to use the faceplates can be found in the online help or the user manual provided for this library Deactivate block icons If you do not need a block icon for every block you can deactivate it 1 Open CFC Editor 2 Select the desired block PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 ...

Page 28: ...ation 3 Right click and select Object properties in the context menu 4 Uncheck the check box for Create block icon PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 28 Getting Started 05 2015 A5E02897713020A RS AB 004 ...

Page 29: ...og by clicking OK 6 Compile and download the CFC if not yet done 7 Compile the OS and activate WinCC The block icon e g SSMEAS is not visible anymore PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 Getting Started 05 2015 A5E02897713020A RS AB 004 29 ...

Page 30: ...Getting Started 4 4 Operator Station PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 30 Getting Started 05 2015 A5E02897713020A RS AB 004 ...

Page 31: ...ess Control System V7 0 Getting Started First Steps Documentation For PCS 7 V7 1 Process Control System PCS 7 Getting Started Part 1 V7 1 Process Control System PCS 7 Getting Started Part 2 V7 1 Programming and Operating Manual PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 Getting Started 05 2015 A5E02897713020A RS...

Page 32: ...References PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 32 Getting Started 05 2015 A5E02897713020A RS AB 004 ...

Page 33: ...nction Chart GSD Generic Station Description HMI Human machine interface HW Config Hardware configuration module in the SIMATIC Manager OS Operator station PCS 7 Process Control System 7 CPU Central Processing Unit SS Soft starter PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 Getting Started 05 2015 A5E02897713020A RS AB 004 33 ...

Page 34: ...List of Abbreviations 6 1 Abbreviations PCS 7 Library Soft Starter 3RW44 V6 2 V7 1 V8 Migration V8 0 SP2 34 Getting Started 05 2015 A5E02897713020A RS AB 004 ...

Reviews: