![Siemens SIPROTEC PROFINET IO Manual Download Page 74](http://html.mh-extra.com/html/siemens/siprotec-profinet-io/siprotec-profinet-io_manual_1265444074.webp)
3 Parameterization
3.2 Parameterization with DIGSI
74
SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
Updating the Parameter Sets of IEC 61850
✧
In DIGSI Manager, right-click the
IEC61850 station
and select the
Object properties...
entry in the menu.
✧
In the
Properties - IEC61850 station
dialog, select the
Update
tab and update the parameter set using
the
Update all parameters
button.
✧
Close the
Report
window and the
Properties - IEC61850 station
dialog.
Initializing the SIPROTEC Device
✧
Right-click the SIPROTEC device in DIGSI Manager.
✧
Click
Initialize device...
in the menu that opens.
✧
Select the
connection type
and the device in the
Initialize device
dialog.
✧
Click OK.
NOTE
To activate the modified parameters, update the parameter set after each time you have made changes in
DIGSI Manager.
NOTE
The SIPROTEC device only has to be initialized once when a new device has been added.
NOTE
The initialization is always performed via the serial front interface or the USB port at the device. Following
successful initialization of the network settings you can now make changes using DIGSI via the Ethernet
module.
com_profinet-io_profile_us.book Page 74 Friday, August 17, 2012 1:40 PM