2 PROFINET IO in SIPROTEC
2.4 IO Modules
32
SIPROTEC 4, Communication Module PROFINET IO, Communication Profile
C53000-L1840-C360-1, Edition 08.2012
IO Module Double-Point Indications 08
IO Module Measured Values 06
Double-point indications 08
Category in the hardware catalog
Input data
Data type
8 double-point indications; see Chapter 2.3.3
Data size
2 bytes
Acyclic reading/writing of data
None
Parameters
Each single-point indication can be assigned to the process alarm
(see Chapter 2.7).
Default setting: all not assigned
Measured values 06
Category in the hardware catalog
Input data
Data type
6 measured values as Float32 value (floating point); see
Chapter 2.3.4
Data size
24 bytes
Acyclic reading of data
Reading of 6 unit IDs as unsigned 16 bit value; see Chapter 2.8.2
Reading from:
•
Slot:
slot number of the plugged module
•
Subslot:
1
•
Index:
100
Acyclic writing of data
None
Parameters
None
com_profinet-io_profile_us.book Page 32 Friday, August 17, 2012 1:40 PM