2.2 Differential Protection
127
7UT613/63x Manual
C53000-G1176-C160-2
Figure 2-45
Summation of the currents in the summation transformer on connection L1-L3-E
For the connection L1-L3-E (see figure 2-44), the weighting factors W of the summa-
tion currents IM for the various fault conditions and the ratios to that given by the three-
phase symmetrical faults are shown in table 2-5. On the right hand side is the comple-
mentary multiple of rated current
I
M
= 100 mA which W/
√
3 would have to be in order
to arrive at the summation current
I
1
. If the current setting values are multiplied with
this factor, the actual pickup values result.
Table 2-5
Fault conditions and weighting factors for the CT connection L1-L3-E
The table shows that the differential protection is more sensitive to earth faults and to
double earth faults than to those without earth path component. This increased sensi-
tivity is due to the fact that the summation transformer winding in the CT starpoint con-
nection (
I
E
, residual current (refer to figure 2-44) has the largest number of turns and
thus the weighting factor W = 3.
If the higher earth current sensitivity is not necessary, connection according to figure
2-46 can be used. This is reasonable in earthed systems with particularly low zero se-
quence impedance where earth fault currents may be larger than those under two-
phase fault conditions. With this connection, the values given in Table 2-6 below can
be recalculated for the seven possible fault conditions in solidly earthed networks.
Fault
W
W/
√
3
I
1
for
I
M
= 100 mA
L1-L2-L3 (sym.)
L1-L2
L2-L3
L3-L1
L1-E
L2-E
L3-E
√
3
2
1
1
5
3
4
1,00
1,15
0,58
0,58
2,89
1,73
2,31
1.00 ·
I
N
0.87 ·
I
N
1.73 ·
I
N
1.73 ·
I
N
0.35 ·
I
N
0.58 ·
I
N
0.43 ·
I
N
Summary of Contents for SIPROTEC 7UT613 series
Page 16: ...Contents 16 7UT613 63x Manual C53000 G1176 C160 2 Literature 631 Glossary 623 Index 633 ...
Page 30: ...1 Introduction 30 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 506: ...A Appendix 506 7UT613 63x Manual C53000 G1176 C160 2 7UT633 D E ...
Page 508: ...A Appendix 508 7UT613 63x Manual C53000 G1176 C160 2 7UT633 P Q ...
Page 510: ...A Appendix 510 7UT613 63x Manual C53000 G1176 C160 2 7UT635 D E ...
Page 512: ...A Appendix 512 7UT613 63x Manual C53000 G1176 C160 2 7UT635 P Q ...
Page 515: ...A 2 Terminal Assignments 515 7UT613 63x Manual C53000 G1176 C160 2 7UT633 B ...
Page 517: ...A 2 Terminal Assignments 517 7UT613 63x Manual C53000 G1176 C160 2 7UT633 N ...
Page 519: ...A 2 Terminal Assignments 519 7UT613 63x Manual C53000 G1176 C160 2 7UT635 B ...
Page 521: ...A 2 Terminal Assignments 521 7UT613 63x Manual C53000 G1176 C160 2 7UT635 N ...
Page 622: ...A Appendix 622 7UT613 63x Manual C53000 G1176 C160 2 ...
Page 632: ...Literature 632 7UT613 63x Manual C53000 G1176 C160 2 ...