External Trip Coupling
267
7UM62 Manual
C53000-G1176-C149-3
2.41
External Trip Coupling
2.41.1 Functional Description
Up to four desired signal from external protection or supervision units can be
incorporated into the processing of 7UM62. The signals are coupled as ”External
signal” via binary inputs. Like the internal protection and supervision signals, they can
be annunciated, time delayed, transmitted to the trip matrix, and blocked. By means
of these signals it is possible to include external protection commands, e.g. from
Buchholz protection or shaft current supervision, into the processing of annunciations
and trip commands of 7UM61. Furthermore, an interaction of protection functions of
different numerical machine protection relays of the series 7UM6 can be performed.
The status of the assigned inputs is checked in cyclic intervals. Alteration of the input
status is considered only after two subsequent status checks with equal result. An
additional time delay
is available for each of the external trip
command channels.
The logic diagram of one external trip command channel is illustrated in Figure 2-128.
In total, the relay incorporates four such channels, i.e. four times this logic. The
illustrated function numbers are valid for the first external trip command channel.
Figure 2-128 Logic Diagram of One External Trip Command Channel
2.41.2 Setting Hints
General
External trip commands via binary inputs are only effective and accessible if during the
configuration of the protective functions the addresses
through
have been set to
Enabled
. Set
Disabled
if the functions are
not required. Addresses
through
are
used to switch the functions individually
ON
or
OFF
, or to block only the trip command
(
Block Relay
).
Like the internal protection and supervision signals, they can be annunciated as
”External trip”, time delayed and transmitted to the trip matrix. The delay times are set
at addresses
through
. Like for the protective
functions, the dropout of the direct input trippings is extended by
parameterized minimum duration.
FNo. 04526
FNo. 04532 etc.
FNo. 04536 etc.
&
FNo. 04523
Tripping
matrix
FNo. 04537 etc.
TMin
TRIP CMD