Frequency Protection (ANSI 81)
157
7UM62 Manual
C53000-G1176-C149-3
2.21.2.1 Settings for the Frequency Protection
2.21.2.2 Information for Frequency Protection
Addr.
Setting Title
Setting Options
Default Setting
Comments
4201
O/U FREQUENCY
OFF
ON
Block relay for trip com-
mands
OFF
Over / Under Frequency Protec-
tion
4202
f1 PICKUP
40.00..65.00 Hz
48.00 Hz
f1 Pickup
4203
f1 PICKUP
40.00..65.00 Hz
58.00 Hz
f1 Pickup
4204
T f1
0.00..600.00 sec
1.00 sec
T f1 Time Delay
4205
f2 PICKUP
40.00..65.00 Hz
47.00 Hz
f2 Pickup
4206
f2 PICKUP
40.00..65.00 Hz
57.00 Hz
f2 Pickup
4207
T f2
0.00..100.00 sec
6.00 sec
T f2 Time Delay
4208
f3 PICKUP
40.00..65.00 Hz
49.50 Hz
f3 Pickup
4209
f3 PICKUP
40.00..65.00 Hz
59.50 Hz
f3 Pickup
4210
T f3
0.00..100.00 sec
20.00 sec
T f3 Time Delay
4211
f4 PICKUP
40.00..65.00 Hz
52.00 Hz
f4 Pickup
4212
f4 PICKUP
40.00..65.00 Hz
62.00 Hz
f4 Pickup
4213
T f4
0.00..100.00 sec
10.00 sec
T f4 Time Delay
4214
THRESHOLD f4
Freq. prot. stage automatic
Freq. prot. stage overfre-
qency
Freq. prot. stage underfre-
qency
Freq. prot. stage
automatic
Handling of Threshold Stage f4
4215
Umin
10.0..125.0 V; 0
65.0 V
Minimum Required Voltage for
Operation
F.No.
Alarm
Comments
05203 >BLOCK Freq.
>BLOCK frequency protection
05206 >BLOCK f1
>BLOCK stage f1
05207 >BLOCK f2
>BLOCK stage f2
05208 >BLOCK f3
>BLOCK stage f3
05209 >BLOCK f4
>BLOCK stage f4
05211 Freq. OFF
Frequency protection is OFF
05212 Freq. BLOCKED
Frequency protection is BLOCKED
05213 Freq. ACTIVE
Frequency protection is ACTIVE
05214 Freq UnderV Blk
Frequency protection undervoltage Blk
05232 f1 picked up
f1 picked up