2.3 Power System Data 1
37
7UM61 Manual
C53000-G1176-C127-3
ATEX100
Parameter
274
ATEX100
allows compliance with PTB requirements (special require-
ments in Germany) for thermal replicas. If this parameter is set to
YES
, all thermal rep-
licas of the 7UM61 are stored on auxiliary power supply failure. As soon as the supply
voltage returns, the thermal replicas continue operating with the stored values. If the
parameter is set to
NO
, the calculated overtemperature values of all thermal replicas
are reset to zero on auxiliary power supply failure.
Command Duration
Address
280
is used to set the minimum time
TMin TRIP CMD
the tripping contacts
will remain closed. This setting applies to all protective functions that initiate tripping.
Current Flow Moni-
toring
Address
281
BkrClosed I MIN
corresponds to the threshold value of the integrated
current flow monitoring feature. This setting is used for the elapsed-time meter and the
overload protection. If the set threshold current is exceeded, the circuit breaker is con-
sidered closed and the power system is considered to be in operation. In the case of
overload protection, this criterion distinguishes between standstill and motion of the
machine to be protected.
2.3.2
Settings
Addresses which have an appended "A" can only be changed with DIGSI, under Ad-
ditional Settings.
The table indicates region-specific presettings. Column C (configuration) indicates the
corresponding secondary nominal current of the current transformer.
Addr.
Parameter
C
Setting Options
Default Setting
Comments
204
CT ANGLE W0
-5.00 .. 5.00
°
0.00
°
Correction Angle CT W0
210
CT Starpoint
towards machine
towards starpt.
towards machine
CT Starpoint
211
CT PRIMARY
10 .. 50000 A
500 A
CT Rated Primary Current
212
CT SECONDARY
1A
5A
1A
CT Rated Secondary
Current
213
FACTOR IEE
1.0 .. 300.0
60.0
CT Ratio Prim./Sec. Iee
221
Unom PRIMARY
0.10 .. 400.00 kV
6.30 kV
Rated Primary Voltage
222
Unom SECONDARY
100 .. 125 V
100 V
Rated Secondary Voltage
(Ph-Ph)
223
UE CONNECTION
neutr. transf.
broken delta
Not connected
any VT
neutr. transf.
UE Connection
224
FACTOR UE
1.0 .. 2500.0
36.4
VT Ratio Prim./Sec. Ue
225A
Uph / Udelta
1.00 .. 3.00
1.73
Matching Ratio Ph.-VT to
Broken-Delta-VT
270
Rated Frequency
50 Hz
60 Hz
50 Hz
Rated Frequency
271
PHASE SEQ.
L1 L2 L3
L1 L3 L2
L1 L2 L3
Phase Sequence
272
SCHEME
Busbar
Unit transf.
Busbar
Scheme Configuration
www
. ElectricalPartManuals
. com