Installation and Commissioning
260
7SS52 V4 Manual
C53000-G1176-C182-3
7.1.3.4
Connection
If you have couplers with one transformer, connect the current inputs of the bay
units in series per phase (Figure 7-1, page 260).
Record the isolator positions according to the configuration via the binary inputs of
the single bay units.
Connect the TRIP command and transfer trip contacts of both bay units in parallel.
In this case also connect further binary input functions (e.g. CBF initiation, CBF re-
lease, TRIP release) in parallel.
Figure 7-1 Connection of the current inputs of the bay units in bus couplers with only one cur-
rent transformer.