Technical Data
10-12
7SA522 Manual
C53000-G1176-C119-2
Measuring tolerances
with sinusoidal quantities
1
) Secondary values based on I
N
= 1 A; for I
N
= 5 A they must be multiplied with 5.
2
) Secondary values based on I
N
= 1 A; for I
N
= 5 A they must be devided by 5.
Times
Shortest trip time
approx. 17 ms (50 Hz) / 15 ms (60 Hz)
Drop-out time
approx. 30 ms
Stage timers
0.00 s to 30.00 s;
∞
(steps 0.01 s)
for all zones;
separate time setting possibilities for
single-phase and multi-phase faults
for the zones Z1, Z2, and Z1B
Time expiry tolerances
1 % of set value or 10 ms
The set times are pure delay times.
Emergency
operation
in case of measured voltage failure,
see Section 10.9
e.g. voltage secondary mcb trip
10.3
Power Swing Supplement
Power swing detection
rate of change of the impedance phasor
and observation of the path curve
Distance between power swing
5
Ω
*)
measuring range PPOL and
fault detection range APOL
Max. power swing frequency
approx. 7 Hz
Power swing blocking programs
Block 1st zone only
Block higher zones
Block 1st and 2nd zone
Block all zones
Out-of-step trip
Trip following instable power swings
(out-of-step)
*) Secondary values based on I
N
= 1 A; for I
N
= 5 A the values are to be divided by 5.
∆
X
X
--------
5 % for 30°
ϕ
sc
90°
≤
≤
≤
∆
R
R
--------
5 % for 0°
ϕ
sc
60°
≤
≤
≤
∆
Z
Z
-------
5 % for –30°
ϕ
sc
ϕ
line
–
30°
≤
≤
≤
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...