Technical Data
10-21
7SA522 Manual
C53000-G1176-C119-2
10.9
Overcurrent Protection
Operating modes
As emergency overcurrent protection or back-up overcurrent protection:
Emergency overcurrent protection
operates on failure of the measured
voltage,
– on trip of a voltage secondary miniature
circuit breaker (via binary input)
– on detection of a fuse failure in the
voltage secondary circuit
Back-up overcurrent protection
operates independent on any events
Characteristics
Definite time stages
(definite)
I
Ph
>>,3I
0
>>, I
Ph
>, 3I
0
>
Inverse time stage
(IDMT)
I
P
, 3I
0P
one of the characteristics according to
Figure 10-2 to 10-2 can be selected
Current Stages
High set stages
I
Ph
>> (phases) 0.10 A to 25.00 A
1
)
(steps 0.01 A)
T
IPh>>
(phases) 0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
3I
0
>> (earth)
0.05 A to 25.00 A
1
)
(steps 0.01 A)
T
3I0>>
(earth)
0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
Overcurrent stages
I
Ph
> (phases)
0.10 A to 25.00 A
1
)
(steps 0.01 A)
T
IPh>
(phases) 0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
3I
0
> (earth)
0.05 A to 25.00 A
1
)
(steps 0.01 A)
T
3I0>
(earth)
0.00 s to 30.00 s
(steps 0.01 s)
or
∞
(ineffective)
Overcurrent stages
I
P
(phases)
0.10 A to 4.00 A
1
)
(steps 0.01 A)
(inverse time acc. IEC)
pick-up at approx. 1.1·set value
T
IP
(phases)
0.05 s to 3.00 s
(steps 0.01 s)
or
∞
(ineffective)
T
IPadd
(phases) 0.00 s to 30.00 s
(steps 0.01 s)
3I
0P
(earth)
0.05 A to 4.00 A
1
)
(steps 0.01 A)
pick-up at approx. 1.1·set value
T
3I0P
(earth)
0.05 s to 3.00 s
(steps 0.01 s)
or
∞
(ineffective)
T
3I0Padd
(earth) 0.00 s to 30.00 s
(steps 0.01 s)
Overcurrent stages
I
P
(phases)
0.10 A to 4.00 A
1
)
(steps 0.01 A)
(inverse time acc. ANSI)
pick-up at approx. 1.1·set value
D
IP
(phases)
0.50 s to 15.00 s
(steps 0.01 s)
or
∞
(ineffective)
T
IPadd
(phases) 0.00 s to 30.00 s
(steps 0.01 s)
3I
0P
(earth)
0.05 A to 4.00 A
1
)
(steps 0.01 A)
pick-up at approx. 1.1·set value
Summary of Contents for siprotec 7SA522
Page 20: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 64: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 89: ...SIPROTEC 4 Devices 4 25 7SA522 Manual C53000 G1176 C119 2 Figure 4 20 CFC Logic example ...
Page 408: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 456: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 516: ...7SA522 Manual C53000 G1176 C119 2 ...
Page 620: ...Appendix B 48 ...