Setting Notes
Averaging
The selection of the time period for measured value averaging is set using the parameter 2801
DMD
Interval
in the corresponding setting group from A to D at MEASUREMENT. The first number specifies the
averaging time window in minutes while the second number gives the frequency of updates within the time
window.
15 Min., 3 Subs
, for example, means: Averaging over time for all measured values that arrive
within a time window of 15 minutes. The output is updated every 15/3 = 5 minutes.
Address 2802
DMD Sync.Time
allows you to specify whether the time period of averaging selected at
address 2801 starts on the hour (
On The Hour
) or whether it is synchronized with any of the other times (
15
After Hour
,
30 After Hour
or
45 After Hour
).
If the settings for averaging are changed, the measured values stored in the buffer are deleted, and new
results for the average calculation are only available after the set time period has passed.
Settings
Addr.
Parameter
Setting Options
Default Setting
Comments
2801
DMD Interval
15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
60 Min., 1 Sub
Demand Calculation Intervals
2802
DMD Sync.Time
On The Hour
15 After Hour
30 After Hour
45 After Hour
On The Hour
Demand Synchronization Time
Information List
No.
Information
Type of
Informa-
tion
Comments
833
I1 dmd=
MV
I1 (positive sequence) Demand
834
P dmd =
MV
Active Power Demand
835
Q dmd =
MV
Reactive Power Demand
836
S dmd =
MV
Apparent Power Demand
963
Ia dmd=
MV
I A demand
964
Ib dmd=
MV
I B demand
965
Ic dmd=
MV
I C demand
1052
Pdmd Forw=
MV
Active Power Demand Forward
1053
Pdmd Rev =
MV
Active Power Demand Reverse
1054
Qdmd Forw=
MV
Reactive Power Demand Forward
1055
Qdmd Rev =
MV
Reactive Power Demand Reverse
Set Points (Measured Values)
Setting Notes
Setpoints for Measured Values
Setting is performed in the DIGSI configuration Matrix under Settings, Masking I/O (Configuration Matrix).
Apply the filter "Measured and Metered Values Only" and select the configuration group "Set Points (MV)".
2.17.7.2
2.17.7.3
2.17.7.4
2.17.8
2.17.8.1
Functions
2.17 Auxiliary Functions
190
SIPROTEC 4, 7SD80, Manual
E50417-G1100-C474-A2, Edition 02.2018
Summary of Contents for SIPROTEC 4 7SD80
Page 8: ...8 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 10: ...10 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 18: ...18 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 248: ...248 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 298: ...298 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 312: ...312 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 322: ...322 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 400: ...400 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...
Page 402: ...402 SIPROTEC 4 7SD80 Manual E50417 G1100 C474 A2 Edition 02 2018 ...