Functional description
I IA CE
SIPLUS RIC IEC on S7 V1.5
Page 20 of 28
©SIEMENS AG 2013
Para_MD
Para pro Info
Create any amount of parameter blocks by setting the array value n in the decla-
ration view accordingly. In the detail view the parameters can be individual ad-
justed.
P_Src_ASDU_Address
ASDU address from the expected information. A ‚0‘ entered here (default) will
switch off the check for the ASDU address. This should be carried out only in
conjunction with a filter at the block input or in conjunction with clear information
object addresses.
P_Src_Info_Address
For each information to be transferred minimum this information object address
(IOA) has to be declared.
The first parameter field with information object address = 0 will be established
during start up. From this all further images are released for the automatically
update.
P_Dst_Info_Address
The transfer of the IEC information is carried out with the IOA specified here.
With
value ‚0‘ the received IOA will be taken without changes.
Res_10
Reserve
Res_11
Reserve
Int_ToDo
Internally use
Im_State_of_TimeStampg
Image:
State of the time stamp of the information
Im_S7_TimeStamp
Image:
Time stamp of the information in S7 format date and time
In this case it is the time from the received message, a combination of CPU time
and time from the message, or the absolute CPU time.
Im_TI_Basic
Basic type identification of the last received message. Basic type identification
and from this FB supported are: 1,3,5,7,9,1,13,15. They represent the infor-
mation types single, double indication, transformer step position, bit pattern,
measurands normalized value, scaled value, short floating point number and
integrated totals
Im_TI
Type identification of the last received message
Im_Value
Actual value of the received information
Measurands are always entered as real value in the Simatic format independent
of the received format.
IM_State
Actual status of the information. Structure according to IEC standard.
At single and double information the state is contained as well.
Diag_Count
Counter which is increased with each reception and with it updating of the image
IM_COT
Cause of transmission (COT) according to IEC standard of the last received
message. The value can be changed from the FB during operation.
IM_Originator
Originator of the last received message (if existing otherwise 0)
P_Threshold_Value
With P_Threshold_Value it is possible to parameterize an individual threshold for
measured values. Without specification (default = 0.0) an optional global thresh-
old specified at the block in
put ‚Threshold_Val_ME‘ is effective.
Value_Last
Internally use
Threshold_Memory
Internally use