Operating Instructions SIPLUS CMS4000 ION BINARYINPUT T001
picture 6 power supply interface
Caution
The device ION BINARYINPUT T001 is designed for operation with safety extra-low voltage. This
means that only safety extra-low voltages (SELV) complying with IEC950/EN60950/VDE0805 can
be connected to the power supply terminals.
The power supply unit for the supply of the ION BINARYINPUT T001 has to meet NEC Class 2
(range of voltage 18-32 V, maximum load of 1 A).
The ION BINARYINPUT T001 has to be protected with a fuse element of double maximum load
and tripping characteristic „medium time lag“ or „time lag“.
Never operate the ION BINARYINPUT T001 with AC voltage or DC voltage higher than 32 VDC.
4.3.3
Binary Interfaces
At the ION BINARYINPUT T001, the interface to the binary 0/24 V signals
CH 01 +/- … CH 08 +/-
is implemented as 16-pin-socket (PHOENIX, MVSTBW 2,5/16-GF-5,08).
Bild 7 binary interfaces
SIPLUS CMS4000 ION BI
Operating Instructions, 03/2010, A5E02185979A-02
13