Siemens SIPLUS CMS4000 ION BINARYINPUT T001 Operating Instructions Manual Download Page 1

Operating Instructions SIPLUS CMS4000 ION BINARYINPUT T001 

 

 

 

 

 

 

 

Preface 

 

 

 

 

Product Overview 

SIPLUS

 

CMS4000  

 

 Installation 

Interface Node 

 

 

 ION BINARYINPUT T001 (ION BI)  

Wiring 

 

 

 

6AT8000-1BA00-2XA0 

Technical Data 

 

 

 

 

Appendix 

 

 

 

 

 

 

Operating Instructions - English 

 

 

Release 2010-03 

  

 

 
 
SIPLUS CMS4000 ION BI 
Operating Instructions, 03/2010, A5E02185979A-02 
 

1

 

 

 

Summary of Contents for SIPLUS CMS4000 ION BINARYINPUT T001

Page 1: ... 1 Product Overview 2 SIPLUS CMS4000 Installation 3 Interface Node ION BINARYINPUT T001 ION BI Wiring 4 6AT8000 1BA00 2XA0 Technical Data 5 Appendix 6 Operating Instructions English Release 2010 03 SIPLUS CMS4000 ION BI Operating Instructions 03 2010 A5E02185979A 02 1 ...

Page 2: ...nd work on the equipment Qualified persons are defined as persons who are authorized to commission to earth and to tag circuits equipment and systems in accordance with established safety practices Intended Use Please note the following Warning This device and its components may only be used for the applications described in the catalog or technical description and only in connection with devices ...

Page 3: ...l 2 6 Product Overview 2 1 6 What is SIPLUS CMS 2 2 7 What is an Interface Node ION BI 2 3 8 Scope of Delivery 3 9 Installation 3 1 9 Type of Installation 3 2 9 Installation 3 3 9 Disassembly 4 11 Wiring 4 1 11 General Rules and Regulations for operation of ION BI 4 2 11 Grounding 4 3 12 Interfaces 4 3 1 12 IEEE1394a Interfaces 4 3 2 12 Power Supply Interface 4 3 3 13 Binary Interfaces 4 3 4 14 In...

Page 4: ...n with current information to new components and updated components 1 3 Validity of this Document This document is valid for the Interface Node ION BI 1 4 Modification compared with the Previous Version Max sampling frequency is 50 kHz Input current 10 2 mA at 24V DC Notice You will find the version of the operating instructions in the number of the footer A5E02185979A 02 1 5 CE Marking The Interf...

Page 5: ... Node ION BI It contains the following topics Installation and wiring Chapter 3 and 4 Technical data Chapter 5 List of abbreviations with explanation of the general definitions of the used terms Chapter 6 1 9 Recycling and Disposal The ION BI is environmental compatibility and recyclable For environmentally compatible recycling and disposal of your old device contact a certified waste disposal for...

Page 6: ...services in industrial plants SIPLUS CMS is a modular scalable analysis and diagnosis system It is optimized for reaction less measurement of analog binary and numerical data SIPLUS CMS can be integrated in existing and new industrial plants SIPLUS CMS can be integrated into the TIA Architecture Picture 1 Typical configuration SIPLUS CMS4000 ION BI Operating Instructions 03 2010 A5E02185979A 02 6 ...

Page 7: ...Area The compact design of the ION BI enables the application in space saving ranges Easy handling of ION BI provides a fast commissioning and maintenance The product is designed for the application on a DIN Rail or for mounting angles Display The device ION BINARYINPUT T001 provides three plugs for further SIPLUS CMS4000 system components and eight inputs for binary 0 24 V signals Picture 2 Front...

Page 8: ...ug in terminal block PHOENIX CONTACT COMBICON 3 Pin MVSTBW 2 5 3 STF 5 08 16 pin plug in terminal block PHOENIX CONTACT COMBICON 16 Pin MVSTBW 2 5 16 STF 5 08 Unpacking and Checking After unpacking please check the packet for completeness and all parts for transport damages Warning Do not use any parts that show signs of damage SIPLUS CMS4000 ION BI Operating Instructions 03 2010 A5E02185979A 02 8...

Page 9: ...tall the plugs of the IEEE1394 connection cables Install the terminal block of the power supply connection cable 1 3 2 picture 3 installation of the ION BINARYINPUT T001 on a DIN rail Caution The spaces which are specified in chapter Appendix paragraph Dimension Drawing on top and under neath the device 25 mm and in front of the device 80 mm have to be kept 3 3 Disassembly Disassembly of electric ...

Page 10: ...PUT T001 Removal of the device from the DIN rail Push the device down against the DIN rail and hang it out SIPLUS CMS4000 ION BI Operating Instructions 03 2010 A5E02185979A 02 10 picture 4 disassembly of the ION BINARYINPUT T001 from the DIN rail 1 3 2 ...

Page 11: ...following alternatives Chart 2 Recommendation for reaching the EMV compability Alternative Notice Controlled power adaptor SITOP SMART EMV Interference filter Company TIMONTA e g Type FMLB 0109 0640 SMD Ferrite on both power supply ledges Company WÜRTH ELEKTRONIK e g No 74271222 Protection against external electrical influences The following chart shows what you have to observe for the protection ...

Page 12: ...ces 4 3 2 Power Supply Interface The connection takes place via a 3 pin plug in terminal block The power supply is connected to the chassis via a low resistance in order to keep a high interference re sistance The supply voltage is attached via pin 1 24V and pin 2 0V The power feed of 24 V on pin 3 PD Power Down of the terminal block of 90 sec onds causes a RESET of the device After approximately ...

Page 13: ...RYINPUT T001 has to meet NEC Class 2 range of voltage 18 32 V maximum load of 1 A The ION BINARYINPUT T001 has to be protected with a fuse element of double maximum load and tripping characteristic medium time lag or time lag Never operate the ION BINARYINPUT T001 with AC voltage or DC voltage higher than 32 VDC 4 3 3 Binary Interfaces At the ION BINARYINPUT T001 the interface to the binary 0 24 V...

Page 14: ...s firmware operates Name ERR Description error indicator Color red Condition off no error on error fan if any Name LNK Description indicator for the connection to the controller Color yellow Condition off no connection to the controller on connection to the controller established blinks data exchange with the controller 4 3 5 Cable Traction Relief Caution You have to prepare adequate cable tractio...

Page 15: ...EN 61000 4 2 2001 EN 61000 4 2 1995 A1 1998 A2 2001 DIN EN 61000 4 3 2008 EN 61000 4 3 2006 A1 2008 DIN EN 61000 4 4 2005 EN 61000 4 4 2004 DIN EN 61000 4 5 2007 EN 61000 4 5 2006 Industry DIN EN 61000 4 6 2008 EN 61000 4 6 2007 Einsatzbereich Anforderungen an Installation Guide Lines The product meets the requirements if you meet the installation instructions and safety related notices as describ...

Page 16: ... of machines This product is not a machine in the sense of the EC Machinery Directive There is therefore no declaration of conformity relating to the EC Machinery Directive 89 392 ECC for this product If the product is part of the equipment of a machine it must be included in the procedure for the declaration of conformity by the manufacturer of the machine ...

Page 17: ...4a Interface P1 P3 Number 3 Connector type 6 pin socket Type IEEE1394a Interface Transfer speed 400 Mbps Standard IEEE1394a Binary Interfaces CH 01 08 Number 8 Connector type 16 pin plug in terminal block Phoenix Contact Type comparator input Input voltage 48 V Input protection 60 V Insulation 0 4 kV Electrical isolation channels are electrically isolated separately Input current 2 5 mA I 3 5 mA S...

Page 18: ...onmental Conditions EMC Ambient temperature during operation 0 55 C Transportation and storage temperature 25 85 C Humidity rating 5 95 not condensing EMC interference emission EN 55011 Class A EMC interference immunity EN 61000 6 2 2005 Degree of protection IP20 Constructive Structure Dimensions H x W x D in mm 200 x 60 2 x 126 5 Design aluminum stainless steel Color silver Weight 1 kg Mounting D...

Page 19: ...Operating Instructions SIPLUS CMS4000 ION BINARYINPUT T001 6 Appendix 6 1 Dimensional Drawing picture 9 Dimensional Drawing SIPLUS CMS4000 ION BI Operating Instructions 03 2010 A5E02185979A 02 19 ...

Page 20: ... the latest information about your products The right documents via our search function under Service Support The bulletin board a worldwide knowledge exchange for users and experts Your local representative for Industry Automation Drives Technologies via our representatives database Information about on site services repairs spare parts and lots more you will find under Support 6 3 List of Abbrev...

Reviews: