SIPART PS2 (6DR5...)
30
A5E03436620-AB, 01/2017
5.4
Parameter
5.4.1
Overview of initialization parameters 1 to 5
Introduction
Parameters 1 to 5 are the same for all versions of the positioner. These parameters are used to adjust the positioner to the
actuator. Normally, setting these parameters is sufficient to be able to operate the positioner on an actuator.
If you want to get to know all details of the positioner, gradually try out the effects of the remaining parameters by systematic
testing.
Note
Factory-set parameter values are printed in bold in the following table.
Overview
Parameter
Function
Parameter values
Unit
1.YFCT
Type of actuator
Normal
Inverted
Part-turn actuator
turn
-turn
Linear actuator
WAY
-WAY
Linear actuator - carrier pin on actuator spindle
FWAY
-FWAY
Linear actuator - external linear potentiometer
(e.g. with cylinder drives)
LWAY
-LWAY
Part-turn actuator with NCS
ncSt
-ncSt
Linear actuator with NCS
ncSL
-ncSL
Linear actuator with NCS and lever
ncSLL
-ncLL
2.YAGL
Rated angle of rotation of positioner shaft
1)
33°
Degrees
90°
3.YWAY
2)
Range of stroke (optional setting)
3)
OFF
mm
5 | 10 | 15 | 20
(Short lever 33°, range of stroke 5 to 20
mm)
25 | 30 | 35
(Short lever 90°, range of stroke 25 to 35
mm)
40 | 50 | 60 | 70 | 90 | 110 | 130
(Long lever 90°, range of stroke 40 to 130
mm)
4.INITA
Initialization (automatic)
NOINI | no / ###.# | Strt
5.INITM
Initialization (manual)
NOINI | no / ###.# | Strt
1)
Set the transmission ratio selector accordingly.
2)
Parameter only appears with "WAY", "-WAY", "ncSLL", and "-ncLL"
3)
If used, the value on the actuator must correspond to the set range of stroke on the lever arm.
Carrier must be set to the value of the actuator travel or, if this value is not scaled, to the next larger scale value.