Battery
Description
The battery lies in an externally accessible battery compartment. The battery compartment is located on the
bottom of the device. You need not open the device when replacing the battery.
If the auxiliary voltage fails, the battery ensures continued operation of the internal clock and storage of
certain data (statistical values, values of thermal models) for at least 6 months. Parameterization, logs, and
fault records are always stored in a fail-safe way in a non-volatile memory.
The device cyclically checks the charge of the battery. The
Battery fault
indication is issued if the actual
voltage falls below the minimum.
[le_SIP5Comp_battery_position, 1, --_--]
Figure 5-1
Position of the Battery Compartment on the SIPROTEC 5 Compact Device
(1)
Battery compartment
(2)
Insulating film
Replacing the Battery
Safety Notes
NOTICE
Exercise caution when replacing the battery.
Noncompliance with the specified measures can result in material damage.
²
Replace the battery only with the type specified in the Technical Data.
5.2
5.2.1
5.2.2
Working on the Device
5.2 Battery
42
SIPROTEC 5 Compact, Hardware Description, Manual
C53000-G5300-C002-3, Edition 12.2021
Summary of Contents for SIP5C
Page 8: ...8 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 16: ...16 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 38: ...38 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 52: ...52 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 66: ...66 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 70: ...70 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 72: ...72 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...
Page 74: ...74 SIPROTEC 5 Compact Hardware Description Manual C53000 G5300 C002 3 Edition 12 2021 ...