![Siemens Sinorix al-deco STD Operating Handbook Download Page 8](http://html.mh-extra.com/html/siemens/sinorix-al-deco-std/sinorix-al-deco-std_operating-handbook_383270008.webp)
Description of the extinguisher system
8
Building Technologies
A54475-A1-A2_EN_05.docx
Fire Safety
01.2018
2
Description of the extinguisher system
2.1
Description of operation
The
automatic CO
2
extinguisher system of the type Sinorix
TM
al-deco STD
is a compact automatic
detection and object extinguisher system for combating fire in metalworking machine tools for which
there is a fire risk. A communication interface and an online measurement system monitor the
extinguisher and provide information regarding the amount of extinguisher that is present in the
extinguisher cylinder.
The communication interface indicates all relevant conditions acoustically and optically, such as
Operational status
System active/inactive
System triggered (Fire alarm)
Extinguisher quantity.
All data that is relevant to safety will be recorded in a data storage unit (Black-Box) and can be read
out with a laptop at any time using a USB interface.
No energy is required for the detection and extinguishing procedure. In case of a power failure, the
communication interface and the online measurement system will continue to be supplied with voltage
for a maximum of 12 hours from a power supply unit using a battery.
Apart from the connection of the EMERGENCY STOP command, the extinguisher system requires no
other integration to the existing controller of the machine tool.
2.2
System concept
Installation example of an Sinorix
TM
al-deco STD extinguisher system:
Key to the major components:
1
Extinguisher container CO
2
7
Detection line steel, D=6x4
2
CO
2
valve (IHP)
8
Pneumatic detection tube LIFDES
3
Pressure switch 1
9
Manual start with pressure gauge
4
Ball valve for activation /
10 Detection line end adapter
deactivation of the extinguisher system
11 Extinguisher line
5
DIMES measurement probe (integrated into valve)
12 Extinguisher nozzles
for the CO
2
volume control
13 Distributor block with pressure switches 2 and 3
6
Communication interface
14 Valve protection cap