Overview
SINAMICS V20 multi-pump control
6
Operating Manual, 05/2018, A5E43416874-002
Note
•
Make sure that the function-specific script files you use is downloaded from the previous
Internet address. Otherwise, alarm A650 may appear reminding you that this script is not
an officially released script. Also, you can download the "SINAMICS V20 Inverter
Operating Instructions" from the link.
•
You can obtain the "SSTAGE.bin" file from the corresponding firmware updating package.
Make sure that the version of the firmware updating package to be downloaded and the
version of your V20 firmware are the same.
•
After you successfully download the script files into the inverter, all parameters used for
this function are automatically set to their default settings. Note that the default settings of
parameters P0731, P0732, P0733, P0734, P0840, P0845, P1200, and P2200, which are
different from their factory defaults, are changed to adapt to the function. To make sure
that the multi-pump control function runs properly, do not manually set the values of
P0840 and P0845 after the function is enabled.
•
Multi-pump control uses PID controller-specific parameters. For more information about
how to configure those parameters, see Section "Setting the PID controller" in
"SINAMICS V20 Inverter Operating Instructions".
•
If you use the motor staging function on the inverter, this function is automatically
disabled after the multi-pump control function is enabled.
Setting parameters
Parameter Function
Setting
P4002
Control of script interpreter This parameter controls the execution of the script.
0: Stop script
1: Start script
Range: 0 to 1 (default setting: 1)
r4003
Status of script interpreter
Displays the status of the script interpreter.
0: Interpreter ready
1: Script loading
2: Script loading failed
3: Script executing
4: Script execution error
5: Script execution complete
Range: 0 to 5 (default setting: 0)
P4004
Script start control
Controls when the script is executed.
0: The script will be executed only when the value of P4002 is changed from 0
to 1.
1: The script will be executed automatically after power-on if P4002 = 1.
Range: 0 to 1 (default setting: 1)
P4030
Multi-pump control script
parameter default
Controls the reset operation of the script parameters. The value change to this
parameter takes effect after the next time the script is started.
0:
Set values of all script parameters to default settings after the script is started.
1: Do not reset.
Range: 0 to 1 (default setting: 1)
Summary of Contents for SINAMICS V20 Inverter
Page 4: ...Table of contents SINAMICS V20 multi pump control 4 Operating Manual 05 2018 A5E43416874 002 ...
Page 8: ...Overview SINAMICS V20 multi pump control 8 Operating Manual 05 2018 A5E43416874 002 ...
Page 24: ...Pump switchover SINAMICS V20 multi pump control 24 Operating Manual 05 2018 A5E43416874 002 ...
Page 28: ...Faults and alarms SINAMICS V20 multi pump control 28 Operating Manual 05 2018 A5E43416874 002 ...