A.2.2
Wiring to the PSAs in the power unit
1. Initiate an external firing pulse inhibit using the connected trigger element. LED "2/OUT"
flashes green/yellow.
After the set delay time t = 0.5 s has elapsed, the safety relay LEDs indicate state "Device ready
for operation, all outputs inactive".
LED
Status
1/device
Green
2/Out
Off
3/IN
Off
4/SF
Off
2. Withdraw the external firing pulse inhibit. The LEDs should again indicate state "Device ready,
all outputs active".
LED
Status
1/device
Green
2/Out
Green
3/IN
Green
4/SF
Off
If a fault has occurred in the feedback circuit "Feedback" (input INF at the safety relay), then
the LED display signals fault "Device ready, feedback signal fault".
LED
Status
1/device
Green
2/Out
Green flashing
3/IN
Green
4/SF
Red flashing
The LEDs indicate that when withdrawing/deactivating the external firing pulse inhibit
(sensor circuits IN1 and IN2 are activated), the feedback circuit at the safety relay was not
closed. The safety-related outputs of the safety relay can only be activated if the feedback
circuit is closed.
Wiring
A.2 Checking the wiring when the function is retrofitted
Two-channel firing pulse inhibit
Function Manual, 07/2021, A5E51227986A
21
Summary of Contents for SINAMICS MV
Page 2: ......
Page 6: ...Table of contents Two channel firing pulse inhibit 4 Function Manual 07 2021 A5E51227986A ...
Page 20: ...Operation Two channel firing pulse inhibit 18 Function Manual 07 2021 A5E51227986A ...
Page 25: ......
Page 26: ... HUPDQ XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP 6LHPHQV DUJH ULYHV SSOLFDWLRQV 9RJHOZHLKHUVWU 1 51 5 ...