A.2
Checking the wiring when the function is retrofitted
A.2.1
Wiring to the tripping device
Requirements
• The wiring to the upstream tripping device must be implemented through two channels
using potential-free contacts.
• A tripping device, e.g. mushroom pushbutton or a safety PLC (F-PLC) must be connected. It
is not permissible that the input terminals are jumpered.
Checking the wiring.
1. Check the wiring from the terminal strip to device connections "T1", "IN1" and "T2", "IN2" of
the safety relay. The safety relay indicates if there is a wiring fault: "Group fault, short-circuit/
cross-circuit fault at the input".
LED
Status
1/device
Off
2/Out
Off
3/IN
Yellow flashing
4/SF
Red
If you have correctly wired up the circuit, when the firing pulse inhibit is not activated, the
safety relay LEDs indicate "Device ready for operation, all outputs active".
LED
Status
1/device
Green
2/Out
Green
3/IN
Green
4/SF
Off
2. Check signal "Firing pulse inhibit request to the Control Unit for pulse inhibit".
If the safety relay indicates state "Device ready for operation, all outputs active", then the
digital input in the control at the Control Unit must have a high signal level. After activating
the firing pulse inhibit, the input changes to the "Low" state.
Wiring
A.2 Checking the wiring when the function is retrofitted
Two-channel firing pulse inhibit
20
Function Manual, 07/2021, A5E51227986A
Summary of Contents for SINAMICS MV
Page 2: ......
Page 6: ...Table of contents Two channel firing pulse inhibit 4 Function Manual 07 2021 A5E51227986A ...
Page 20: ...Operation Two channel firing pulse inhibit 18 Function Manual 07 2021 A5E51227986A ...
Page 25: ......
Page 26: ... HUPDQ XUWKHU QIRUPDWLRQ ZZZ VLHPHQV FRP 6LHPHQV DUJH ULYHV SSOLFDWLRQV 9RJHOZHLKHUVWU 1 51 5 ...