Damage caused by incorrect parameter assignment
Malfunctions can occur if you change parameters.
• Do not change the parameters, e.g. for the motor circuit-breaker.
8.2
Parameters
Note
To complement these operating instructions, the List Manual contains an overview of all
parameters as well as a selection of function diagrams to describe the operating principle.
The drive is adapted to the relevant drive task by means of parameters. Each parameter is
identified by a unique parameter number and specific attributes. Such attributes are, for
example:
• Readable attributes
• Writable attributes
• BICO attributes
The parameters can be accessed via the following means:
• PC with commissioning tool via PROFIBUS
• Operator panel
Parameter types
The following parameters are available:
• Adjustable parameters (write/read)
Adjustable parameters directly influence the response of a function, e.g. the ramp-up and
ramp-down time of a ramp-function generator.
• Visualization parameters (read-only)
Display parameters are used to display internal variables, e.g. the actual motor current.
3DUDPHWHU
UHDGU
UHDGZULWHS
%,&2RXWSXW
1RUPDOUHDG
SDUDPHWHUV
%,&2LQSXW
1RUPDOUHDGZULWH
SDUDPHWHUV
Figure 8-1
Parameter types
All these drive parameters can be read and changed via PROFIBUS using the mechanisms
defined in the PROFIdrive profile.
Operation
8.2 Parameters
3rd Party LCI Control Upgrade
100
Operating Instructions, 02/2022, A5E31872818