S>@
Set TM31.AO_char. x2 to 100.00 %.
S>@
Set TM31.AO_char. y2 to 10.000 V.
8.5.2.3
Scaling the input signal of the analog inputs
In addition to the expanded setting options of the analog inputs, a function for scaling the input
signal is available.
Adjustable parameters of the scaling
Parameter
Value
Adjustment range
p4057[0]
Analog inputs, characteristic value x1
-20,000 to 20,000 V or mA
Default settings: 0,000 mA
Setting for the x coordinate in V or mA of the first point on the scaling characteristic.
When analog input 0 is set as a voltage input (p4056 = 0 / 4) and switch S5.0 is set to "V", the unit is V.
When analog input 0 is set as a current input (p4056 = 2 / 3 / 5) and switch S5.0 is set to "I", the unit is
mA.
Parameter
Value
Adjustment range
p4058[0]
Analog inputs, characteristic value y1
-1000.00 to 1000.00%
Default settings: 0,0 %
Setting for the y coordinate in % of the first point on the scaling characteristic.
Parameter
Value
Adjustment range
p4059[0]
Analog inputs, characteristic value x2
-20,000 to 20,000 V or mA
Default settings: 0.000 mA
Setting for the x coordinate in V or mA of the first point on the scaling characteristic.
When analog input 0 is set as a voltage input (p4056 = 0 / 4) and switch S5.0 is set to "V", the unit is V.
When analog input 0 is set as a current input (p4056 = 2 / 3 / 5) and switch S5.0 is set to "I", the unit is
mA.
Parameter
Value
Adjustment range
p4060[0]
Analog inputs, characteristic value y1
-1000.00 to 1000.00%
Default settings: 100,00 %
Setting for the y coordinate in % of the second point on the scaling characteristic.
Operation
8.5 Functions
SINAMICS GM150 6SL3835-2LN44-2AA0
156
Operating Instructions Rev.201910281250 MUSTER
Summary of Contents for Sinamics GM150 6SL3835-2LN44-2AA0
Page 2: ...28 10 2019 12 50 V32 00 ...
Page 232: ...Index SINAMICS GM150 6SL3835 2LN44 2AA0 232 Operating Instructions Rev 201910281250 MUSTER ...
Page 233: ......
Page 236: ......
Page 238: ......