Technical data
C.5 Technical data for operation
Installation and Operating Instructions SINAMICS G180
200
Operating Instructions, 02/2019, 4BS0751-007
C.5
Technical data for operation
Make sure that the following environmental conditions for operation are fulfilled.
The inverters are designed for indoor installation.
●
Class 3K3 environmental conditions in accordance with EN 60721
●
Pollution degree 2
●
Overvoltage category 3
●
Degree of protection IP20 for compact units
●
Degree of protection IP21 for cabinet units
Environmental conditions for the inverter application
Climatic conditions
Class 3K3 according to EN 60721-3-3
Atmospheric pressure
860 mbar … 1060 mbar, corresponds to max. 1000 m above sea level
1)
Ambient temperature
0 °C … + 40 °C
1)
Humidity rating
5 % … 95 %, 1 g/m³ … 25 g/m³
Mechanical conditions
Class 3M4 acc. to EN 60721-3-3
Vibration load
- Deflection
- Acceleration
0.075 mm at 10 ... 58 Hz
10 m/s² at 58 ... 200 Hz
Shock load
- Acceleration
100 m/s² at 11 ms
Chemical conditions
Class 3C2 according to EN 60721-3-3
Biological conditions
Class 3B1 according to EN 60721-3-3
1)
The units can be operated under different environmental conditions if derating is applied.
For further information, refer to Chapter "Derating" (Page 206).