background image

MODEL: W2XF

Space-saving Dual Output Signal Conditioners

Mini-MW Series

LINEARIZER

(PC programmable)
Functions & Features
• Accepting non-linear input and providing a linearized
output, proportional to the process variables
• 101-point calibration
• PC programmable
• High-density mounting

Typical Applications
• V-notch weir
• Gas analyzer
• Irregular-shaped tank level input for volume calculation
• Square root extracting for DP transmitter

89

(3.51)

29.5 (1.16)

124

(4.88)

mm (inch)

MODEL: W2XF–[1][2][3]-[4][5]

ORDERING INFORMATION

• Code number: W2XF-[1][2][3]-[4][5]
Specify a code from below for each [1] through [5].
(e.g. W2XF-S2Z1V3-M2/N/Q)
• Input range (e.g. 1 – 5 V DC)
• Output 1 range (e.g. 4 – 20 mA DC)
• Output 2 range  (e.g. 1 – 5 V DC)
• Specify the specification for option code ‘Q.’
(e.g. /C01/S01)
Note: If one of the outputs should be a current range,
specify it for the Output 1 to allow a greater load.

[1] INPUT

Current

Z1: Range 0 – 50 mA DC (Input resistance 24.9 Ω)

Voltage

S1: Range -1 – +1 V DC (Input resistance 1 MΩ min.)
S2: Range -10 – +10 V DC (Input resistance 1 MΩ min.)
(Configurator software is used to change the input type and

precise range.)

[2] OUTPUT 1

Current

Z1: Range 0 – 20 mA DC

Voltage

V2: Range -10 – +10 V DC
V3: Range -5 – +5 V DC

[3] OUTPUT 2

Same range availability as Output 1
Y: None
(Configurator software is used to change output over the
described range of the selected suffix code.
For changing between suffix codes, set the Output Range
Selector on the side of unit before software adjustment.)

[4] POWER INPUT

AC Power

M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
 47 – 66 Hz)

DC Power

R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[5] OPTIONS (multiple selections)

Standards & Approvlas (must be specified)

/N: Without CE

Other Options

blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)

/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

TERMINAL SCREW MATERIAL

/S01: Stainless steel

RELATED PRODUCTS

• PC configurator software (model: W2CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the
PC.  Please refer to the internet software download site or
the users manual for the PC configurator for applicable
cable types.

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for Mini-MW Series

Page 1: ...nt Z1 Range 0 20 mA DC Voltage V2 Range 10 10 V DC V3 Range 5 5 V DC 3 OUTPUT 2 Same range availability as Output 1 Y None Configurator software is used to change output over the described range of the selected suffix code For changing between suffix codes set the Output Range Selector on the side of unit before software adjustment 4 POWER INPUT AC Power M2 100 240 V AC Operational voltage range 8...

Page 2: ...r range can be any specific value within the output range provided that the minimum span is maintained Load resistance Output drive 12 V max for Output 1 7 V max for Output 2 e g 4 20 mA 600 Ω 12 V 20 mA If not specified the output range is 4 20 mA DC DC Voltage Code V2 wide spans Operational range 11 5 11 5 V DC Minimum span 1 V Code V3 narrow spans Operational range 6 6 V DC Minimum span 0 5 V O...

Page 3: ...onfiguration DIP SW OFF ON 1 2 3 4 OFF ON 1 2 3 4 Provided only for two output type Refer to the instruction manual for detailed procedures EXTERNAL DIMENSIONS TERMINAL ASSIGNMENTS unit mm inch 4 8 7 10 23 91 89 3 50 84 3 31 10 39 22 87 59 2 32 DIN RAIL 35mm wide 4 16 11 M3 SCREW 72 2 83 29 5 1 16 53 2 09 2 4 2x5 17x 20 MTG HOLE 6 24 deep 114 4 49 11 5 6 1 2 3 9 6 23 When mounting no extra space i...

Page 4: ...enclosed by broken line is only with 2nd output option DIP SW DIP SW Digital Computation Low Drift Amplifier STATUS CONFIGURATOR JACK CURRENT Z1 VOLTAGE S1 S2 24 9Ω Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SENTRONICAG ...

Page 5: ...pply and input signal for safety ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ven tilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 5 to 55 C 23 to 131 F with relative humidity within 30 to 90 RH ...

Page 6: ...cted according to the connection diagram 2 Check DIP switch setting 3 Power input voltage Check voltage across the terminal 10 11 with a multimeter 4 Input Check that the input signal is within 0 100 of the full scale 5 Output Check that the load resistance meets the de scribed specifications 6 LED Confirm that the LEDs indicate the normal oper ating mode DIN Rail 35mm wide Spring Loaded DIN Rail ...

Page 7: ...ee front LEDs LD1 LD2 LD3 indicate the transmitter s operating status by different flashing pat terns Examples are shown below LD1 LD2 LD3 A LD1 LD2 LD3 G LD1 LD2 LD3 R NORMAL OPERATION RUN MODE ERROR MODE Parameter Error Error occurred when reading parameters from the internal memory LD1 LD2 LD3 A A G Overrange Input The input is below 15 or above 115 G G A PC Configuration RUN Mode The transmitt...

Page 8: ...11 M3 SCREW 72 2 83 29 5 1 16 53 2 09 2 4 2x5 17x 20 MTG HOLE 6 24 deep 114 4 49 11 5 6 1 2 3 9 6 23 When mounting no extra space is needed between units 4 16 Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SENTRONICAG ...

Reviews: