MODEL: W2XF

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3 screw terminals (torque 0.8 N·m)
Housing material: Flame-resistant resin (black)
Isolation: Input to output 1 to output 2 to power
Overrange output: -15 to +115 %
(Negative current output is not available.)
Zero adjustment: -5 to +5 % (PC programming)
Span adjustment: 95 to 105 % (PC programming)
Programming: Downloaded from PC; input range, output
range, zero and span,
response time, linearization table, simulating output, etc.
Linearization: 101 points max. within the range of
-15 – +115 % input or output; represented as percentage of
full-scale (No table setting is done at shipping. [gain = 1])
Status indicator LED: Tri-color (green/amber/red) LED;
Flashing patterns indicate operation status of the
transmitter.
Configurator connection: 2.5 dia. miniature jack;
RS-232-C level

INPUT SPECIFICATIONS

■ DC Current: Input resistor incoporated
(If not specified, the input range is 4 – 20 mA DC.)
Input range: 0 – 50 mA DC
Minimum span: 2 mA
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
■ DC Voltage
Code S1 (narrow spans)
Input range: -1 – +1V DC
Minimum span: 100 mV
Code S2 (wide spans)
Input range: -10 – +10 V DC
Minimum span: 1 V
Offset: Lower range can be any specific value within the
input range provided that the minimum span is maintained.
If not specified, the input range is shown below.
S1: 0 – 100 mV DC
S2: 1 – 5 V DC

OUTPUT SPECIFICATIONS

■ DC Current
Operational range: 0 – 23 mA DC
Minimum span: 1 mA
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
Load resistance: Output drive 12 V max. for Output 1; 7 V
max. for Output 2
(e.g. 4 – 20 mA: 600 Ω [12 V/20 mA])

If not specified, the output range is 4 – 20 mA DC.
■ DC Voltage
Code V2 (wide spans)
  Operational range: -11.5 – +11.5 V DC
  Minimum span: 1 V
Code V3 (narrow spans)
  Operational range: -6 – +6 V DC
  Minimum span: 0.5 V
Offset: Lower range can be any specific value within the
output range provided that the minimum span is
maintained.
Load resistance: Output drive 1 mA max.
 (e.g. 1 – 5 V: 5000 Ω [5 V/1 mA])
If not specified, the output range is shown below.
V2: 0 – 10 V DC
V3: 1 – 5 V DC

INSTALLATION

Power Consumption
•AC:
 Approx. 5 VA at 100 V
 Approx. 6 VA at 200 V
 Approx. 7 VA at 264 V
•DC: Approx. 3 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lbs)

PERFORMANCE in percentage of span

Overall accuracy:
Input ac output accuracy [gain ≤ 1]
(inp. ac out. accuracy) × gain [gain > 1]
Inversely proportional to the span.
See CALCULATION EXAMPLES OF OVERALL ACURACY.
• Input accuracy: (% of max. input range)
-1 – +1 V : ±0.01 %
-10 – +10 V : ±0.01 %
0 – 50 mA : ±0.02 %
• Output accuracy: ±0.04 % of max. output range
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span
at -5 to +55°C [23 to 131°F]
Response time: (0 – 90 %)
Standard: ≤ 500 msec.
Fast: ≤ 25 msec.
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute (input to output
1 to output 2 to power to ground)

Rugghölzli 2
CH - 5453 Busslingen

Tel. +41 (0)56 222 38 18

Fax +41 (0)56 222 10 12

[email protected]

www.sentronic.com

Produkte, Support und Service

SENTRONIC

AG

Summary of Contents for Mini-MW Series

Page 1: ...nt Z1 Range 0 20 mA DC Voltage V2 Range 10 10 V DC V3 Range 5 5 V DC 3 OUTPUT 2 Same range availability as Output 1 Y None Configurator software is used to change output over the described range of the selected suffix code For changing between suffix codes set the Output Range Selector on the side of unit before software adjustment 4 POWER INPUT AC Power M2 100 240 V AC Operational voltage range 8...

Page 2: ...r range can be any specific value within the output range provided that the minimum span is maintained Load resistance Output drive 12 V max for Output 1 7 V max for Output 2 e g 4 20 mA 600 Ω 12 V 20 mA If not specified the output range is 4 20 mA DC DC Voltage Code V2 wide spans Operational range 11 5 11 5 V DC Minimum span 1 V Code V3 narrow spans Operational range 6 6 V DC Minimum span 0 5 V O...

Page 3: ...onfiguration DIP SW OFF ON 1 2 3 4 OFF ON 1 2 3 4 Provided only for two output type Refer to the instruction manual for detailed procedures EXTERNAL DIMENSIONS TERMINAL ASSIGNMENTS unit mm inch 4 8 7 10 23 91 89 3 50 84 3 31 10 39 22 87 59 2 32 DIN RAIL 35mm wide 4 16 11 M3 SCREW 72 2 83 29 5 1 16 53 2 09 2 4 2x5 17x 20 MTG HOLE 6 24 deep 114 4 49 11 5 6 1 2 3 9 6 23 When mounting no extra space i...

Page 4: ...enclosed by broken line is only with 2nd output option DIP SW DIP SW Digital Computation Low Drift Amplifier STATUS CONFIGURATOR JACK CURRENT Z1 VOLTAGE S1 S2 24 9Ω Specifications are subject to change without notice Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SENTRONICAG ...

Page 5: ...pply and input signal for safety ENVIRONMENT Indoor use When heavy dust or metal particles are present in the air install the unit inside proper housing with sufficient ven tilation Do not install the unit where it is subjected to continuous vibration Do not subject the unit to physical impact Environmental temperature must be within 5 to 55 C 23 to 131 F with relative humidity within 30 to 90 RH ...

Page 6: ...cted according to the connection diagram 2 Check DIP switch setting 3 Power input voltage Check voltage across the terminal 10 11 with a multimeter 4 Input Check that the input signal is within 0 100 of the full scale 5 Output Check that the load resistance meets the de scribed specifications 6 LED Confirm that the LEDs indicate the normal oper ating mode DIN Rail 35mm wide Spring Loaded DIN Rail ...

Page 7: ...ee front LEDs LD1 LD2 LD3 indicate the transmitter s operating status by different flashing pat terns Examples are shown below LD1 LD2 LD3 A LD1 LD2 LD3 G LD1 LD2 LD3 R NORMAL OPERATION RUN MODE ERROR MODE Parameter Error Error occurred when reading parameters from the internal memory LD1 LD2 LD3 A A G Overrange Input The input is below 15 or above 115 G G A PC Configuration RUN Mode The transmitt...

Page 8: ...11 M3 SCREW 72 2 83 29 5 1 16 53 2 09 2 4 2x5 17x 20 MTG HOLE 6 24 deep 114 4 49 11 5 6 1 2 3 9 6 23 When mounting no extra space is needed between units 4 16 Rugghölzli 2 CH 5453 Busslingen Tel 41 0 56 222 38 18 Fax 41 0 56 222 10 12 mailbox sentronic com www sentronic com Produkte Support und Service SENTRONICAG ...

Reviews: