p0641[0...n]
CI: Current limit, variable / Curr lim var
Access level: 3
Calculated: -
Data type: Unsigned32 /
FloatingPoint32
Can be changed: T
Scaling: PERCENT
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 6640
Min:
-
Max:
-
Factory setting:
1
Description:
Sets the signal source for the variable current limit.
The value is referred to p0640.
p0644[0...n]
Current limit excitation induction motor / Imax excitat ASM
CUG120XA_USS
(PM330)
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
50.0 [%]
Max:
300.0 [%]
Factory setting:
300.0 [%]
Description:
Maximum excitation current of the induction motor referred to the permissible rated current of the power unit (r0207[0]).
Dependency:
Only effective for vector control.
Note
The parameter is pre-assigned in the automatic calculation for chassis power units.
p0650[0...n]
Actual motor operating hours / Oper hours motor
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [h]
Max:
4294967295 [h]
Factory setting:
0 [h]
Description:
Displays the operating hours for the corresponding motor.
The motor operating time counter continues to run when the pulses are enabled. When the pulse enable is withdrawn,
the counter is held and the value saved.
Dependency:
See also: p0651
See also: A01590
Note
For p0651 = 0, the operating hours counter is disabled.
The operating hours counter in p0650 can only be reset to 0.
The operating hours counter only runs with drive data set 0 and 1 (DDS).
p0651[0...n]
Motor operating hours maintenance interval / Mot t_op maint
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: MDS, p0130
Unit group: -
Unit selection: -
Function diagram: -
Min:
0 [h]
Max:
150000 [h]
Factory setting:
0 [h]
Description:
Sets the service/maintenance intervals in hours for the appropriate motor.
An appropriate message is output when the operating hours set here are reached.
Dependency:
See also: p0650
See also: A01590
Parameters
7.3 Parameters
SINAMICS G120XA converter