9.2.7
Replace the fan unit for the heat sink
Inverters, frame sizes FSA … FSF have a fan unit for the heat sink. The fan unit for the heat
sink is located at the lower side of the inverter.
When must the fan unit be replaced?
A defective fan unit in operation results in an overtemperature condition of the inverter. For
example, the following messages indicate that the fan unit is defective:
● A05002 (air intake overtemperature)
● A05004 (rectifier overtemperature)
● F30004 (heat sink overtemperature)
● F30024 (temperature model overtemperature)
● F30025 (chip overtemperature)
● F30035 (air intake overtemperature)
● F30037 (rectifier overtemperature)
Remove fan unit, FSA ... FSC
/RFNLQJODWFKHV
/RFNLQJODWFKHV
3RZHU
FRQQHFWRU
3RZHU
FRQQHFWRU
)UDPH6L]H$
)UDPH6L]H&
Figure 9-1
Remove fan unit for heat sink
Corrective maintenance
9.2 Replacing inverter components
SINAMICS G120C converter
Operating Instructions, 09/2017, FW V4.7 SP9, A5E34263257B AF
385