Version 1.0 March 1, 2000
Page 17
1.3 Basic Start-up without Motor Connected to Load
1.3.1 Volts/Hz without Encoder
P060 = 5
P071 = ?
P095 = ?
P097 = ?
P101 = 460
P102 = xxx
P104 = ?
P105 = ?
P060=5
Select “Drive Settings”
P071 = Input Line Voltage
AC-AC Converter=460Volt
DC-AC Inverter = 620Volt
P095 = Select Motor Type
2: Asynchronous 1PH7 Motor
10: IEC Induction Motor
11: NEMA Induction Motor
P097 = Motor Code number for
1PH7 motor (See Appendix)
Motor Nameplate Information
P101= Motor Voltage (V)
P102 = Motor Rated Current (A)
P104 = Cos (phi) per nameplate
P105 = Rated Horsepower
P095 = 10 11
P095 = 2 10 or 11