1.2
Requirements
Supported control units
The "horizontal" installation type has been released exclusively for the following control units:
Control unit
Order number
Minimum required HW version
SIMOTION D425-2 DP
6AU1425-2AA00-0AA0
D
SIMOTION D425-2 DP/PN
6AU1425-2AD00-0AA0
D
SIMOTION D435-2 DP
6AU1435-2AA00-0AA0
D
SIMOTION D435-2 DP/PN
6AU1435-2AD00-0AA0
D
SIMOTION D445-2 DP/PN
6AU1445-2AD00-0AA0
C
SIMOTION D455-2 DP/PN
6AU1455-2AD00-0AA0
C
SIMOTION CX32-2
6AU1432-2AA00-0AA0
B
Note
Different mounting positions than those described in this document or in the
SIMOTION D4x5-2
Commissioning and
Hardware Installation Manual are not permitted!
In order to achieve a low overall height with SINAMICS S120 power units, use SINAMICS S120 Booksize Compact power
units or PM340 power modules connected via the CUA31/CUA32 control unit adapter.
Heat dissipation
If SIMOTION D4x5-2 control units are mounted horizontally, a double fan / battery module is required as in the standard
mounting position.
The double fan / battery module is always contained in the scope of delivery of the control unit for the SIMOTION D4x5-2.
Accessories
Order number
Double fan / battery module incl. battery
6FC5348-0AA02-0AA0
CAUTION
SIMOTION D4x5-2 control units can have a high surface temperature particularly on the aluminum front and the top of the
module especially with the "horizontal" installation type. Perform a module and cable replacement only when the module
has cooled down.
The ventilation spaces of 80 mm must be complied with, see Fig. "Installation of the SIMOTION D4x5-2 in a horizontal
position". The control cabinet cooling concept must also ensure that the maximum air inlet temperature and the ambient
temperature do not exceed 55° C.
Table 1-1
Requirements for the heat dissipation
Requirement
SIMOTION D4x5-2
SIMOTION CX32-2
Double fan / battery module
Always required
-
Clearances
80 mm (measured from the top or
bottom edge of the module)
80 mm (measured from the top or
bottom edge of the module)
Max. ambient temperature
55° C
55° C
Max. air inlet temperature
55° C
55° C
2
Installing
The D4x5-2/CX32-2 are fixed in the same way as in the standard "vertical installation" mounting position.
SIMOTION D4x5-2 Alternative Mounting Position
12