Commissioning
7.3 Switching on
1MB..1/2/3/4 - shaft heights 63 ... 355
96
Operating Instructions, 06/2020, A5E44455710A
5.
In case of uneven running or abnormal noise, switch off the machine. As the machine
runs down, identify the cause.
–
If the mechanical operation improves immediately after the machine is switched off,
then the cause is magnetic or electrical.
–
If the mechanical running does not improve immediately after switching the machine
off, then the cause is mechanical.
- Imbalance of the electrical machine or the driven machine
- The machine set has not been adequately aligned
- The machine is being operated at the system resonance point. System = motor, base
frame, foundation, ...
NOTICE
Serious damage to the machine
If the vibration values in operation are not maintained in accordance with DIN ISO
10816-3, then the machine can be mechanically destroyed.
•
During operation, observe the vibration values in accordance with
DIN ISO 10816-3.