4.4
Space required for ventilation
Maintain a clearance for the air intake where the machine is located (A). Provide sufficient
space where the machine is located so that the fan cover can be removed and mounted as
required. The necessary space requirements are listed in the following table:
Table 4-1
Space required to ventilate the machine
Type
Space requirement / clearance A
1L.….-3A…-….
1M.….-3A…-….
200 mm
1L.….-3B…-….
1M.….-3B…-….
220 mm
1L.….-4A…-….
1M.….-4A…-….
260 mm
1L.….-4B…-….
1M.….-4B…-….
320 mm
$
4.5
Thermal motor protection
The machine is equipped with measuring equipment for direct monitoring of the motor
temperature to protect the machine against overload during operation. Plan a corresponding
circuit for monitoring.
4.6
Thermal motor protection using PTC thermistors (option)
The machine is equipped with PTC thermistors for direct monitoring of the motor temperature
to protect the machine against overheating during operation. Plan a corresponding circuit for
monitoring.
Preparations for use
4.4 Space required for ventilation
SIMOTICS FD 1MM1
32
Operating Instructions 02/2019
Summary of Contents for SIMOTICS FD 1MM1 Series
Page 2: ...05 02 2019 16 03 V11 01 ...
Page 30: ...Description SIMOTICS FD 1MM1 30 Operating Instructions 02 2019 ...
Page 142: ...Maintenance 9 2 Corrective Maintenance SIMOTICS FD 1MM1 142 Operating Instructions 02 2019 ...
Page 166: ...Disposal 11 5 Disposal of components SIMOTICS FD 1MM1 166 Operating Instructions 02 2019 ...
Page 168: ...Service and Support SIMOTICS FD 1MM1 168 Operating Instructions 02 2019 ...
Page 172: ...Quality documents SIMOTICS FD 1MM1 172 Operating Instructions 02 2019 ...
Page 177: ......