Table 6-6
Maximum voltage peaks at the motor terminals for motors specifically designed for converter operation
Rated motor voltage
V
Maximum peak voltage at the motor terminals
Û
phase-to-phase
V
pk
Û
phase-to-ground
V
pk
DC link U
DC
V
≤ 500 V
1600
1400
750
> 500 V to 690 V
2200
1500
1080
Depending on the step height, the voltage rise times for the individual voltage steps in the line-
to-ground voltage at the motor end of the cable must not fall below the following values.
Table 6-7
Rise times as a function of voltage level
Step height
V
Minimum rise time t
r
ns
900
100
1050
200
1260
400
See also
6.8
Final checks
Before closing the terminal box/terminal base of the machine enclosure, check the following:
• Establish the electrical connections in the terminal box in accordance with the information
in this documentation.
• Maintain the air clearances between non-insulated parts as described in Chapter Minimum
• Avoid protruding wire ends.
• In order not to damage the cable insulation, freely arrange the connecting cables.
• Connect the machine corresponding to the specified direction of rotation.
• Keep the inside of the terminal box clean and free from trimmed-off ends of wire.
• Ensure that all seals and sealing surfaces are undamaged and clean.
• Correctly and professionally close unused openings in the terminal boxes. Observe the
information in this documentation.
• Observe the information on torques in this documentation.
See also
Tightening torques for screw and bolt connections (Page 131)
Electrical connection
6.8 Final checks
1FZ shaft height 280
Operating Instructions, 02/2022, A5E51698698A
75